Evaluation of the heat and energy performance of a datacenter by a new efficiency index: Energy Usage Effectiveness Design - EUED

Detalhes bibliográficos
Autor(a) principal: Santos, Alexandre F.
Data de Publicação: 2019
Outros Autores: Souza, Heraldo J. L. de, Gaspar, Pedro Dinis
Tipo de documento: Artigo
Idioma: eng
Título da fonte: Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)
Texto Completo: http://hdl.handle.net/10400.6/7528
Resumo: Data Centers are growing steadily worldwide and they are expected to continue on growing up to 53% in 2020. Due to this growth the energy efficiency in this type of building is essential. There are methodologies to measure this efficiency; one example is PUE (Power Usage Effectiveness). The unit suggested for measuring efficiency at the design stage would be the EUED (Energy Usage Efficiency Design) with this will be used data to use "free cooling" and adiabatic system in some cases, a comparison will be made only considering the equipment in the worst situation. It also uses the study of enthalpy utilization as a new methodology to obtain the results. By doing so, differences were found, between cities than 1.21% of São Paulo in relation to Curitiba and 10.61% of Rio de Janeiro in relation to Curitiba. The indices obtained by applying the EUED index were 1.245 kW.kW- 1 for Curitiba, 1.260 kW.kW-1 for São Paulo and 1.377 kW.kW-1 for Rio de Janeiro, respectively, giving a difference of 16.86% for Curitiba of 16.19% for São Paulo and 10.31% for Rio de Janeiro in relation to PUE COA (Power Usage Effectiveness Constant Outdoor Air).
id RCAP_2e4551b26e4f93040cf84bd9fd734552
oai_identifier_str oai:ubibliorum.ubi.pt:10400.6/7528
network_acronym_str RCAP
network_name_str Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)
repository_id_str 7160
spelling Evaluation of the heat and energy performance of a datacenter by a new efficiency index: Energy Usage Effectiveness Design - EUEDData CentersPUEEUEDData Center CoolingData Centers are growing steadily worldwide and they are expected to continue on growing up to 53% in 2020. Due to this growth the energy efficiency in this type of building is essential. There are methodologies to measure this efficiency; one example is PUE (Power Usage Effectiveness). The unit suggested for measuring efficiency at the design stage would be the EUED (Energy Usage Efficiency Design) with this will be used data to use "free cooling" and adiabatic system in some cases, a comparison will be made only considering the equipment in the worst situation. It also uses the study of enthalpy utilization as a new methodology to obtain the results. By doing so, differences were found, between cities than 1.21% of São Paulo in relation to Curitiba and 10.61% of Rio de Janeiro in relation to Curitiba. The indices obtained by applying the EUED index were 1.245 kW.kW- 1 for Curitiba, 1.260 kW.kW-1 for São Paulo and 1.377 kW.kW-1 for Rio de Janeiro, respectively, giving a difference of 16.86% for Curitiba of 16.19% for São Paulo and 10.31% for Rio de Janeiro in relation to PUE COA (Power Usage Effectiveness Constant Outdoor Air).The 25th IIR International Congress of Refrigeration (ICR 2019)uBibliorumSantos, Alexandre F.Souza, Heraldo J. L. deGaspar, Pedro Dinis2019-11-06T11:33:59Z20192019-01-01T00:00:00Zinfo:eu-repo/semantics/publishedVersioninfo:eu-repo/semantics/articleapplication/pdfhttp://hdl.handle.net/10400.6/7528eng10.18462/iir.icr.2019.0885info:eu-repo/semantics/openAccessreponame:Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)instname:Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informaçãoinstacron:RCAAP2023-12-15T09:46:58Zoai:ubibliorum.ubi.pt:10400.6/7528Portal AgregadorONGhttps://www.rcaap.pt/oai/openaireopendoar:71602024-03-20T00:48:01.686895Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos) - Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informaçãofalse
dc.title.none.fl_str_mv Evaluation of the heat and energy performance of a datacenter by a new efficiency index: Energy Usage Effectiveness Design - EUED
title Evaluation of the heat and energy performance of a datacenter by a new efficiency index: Energy Usage Effectiveness Design - EUED
spellingShingle Evaluation of the heat and energy performance of a datacenter by a new efficiency index: Energy Usage Effectiveness Design - EUED
Santos, Alexandre F.
Data Centers
PUE
EUED
Data Center Cooling
title_short Evaluation of the heat and energy performance of a datacenter by a new efficiency index: Energy Usage Effectiveness Design - EUED
title_full Evaluation of the heat and energy performance of a datacenter by a new efficiency index: Energy Usage Effectiveness Design - EUED
title_fullStr Evaluation of the heat and energy performance of a datacenter by a new efficiency index: Energy Usage Effectiveness Design - EUED
title_full_unstemmed Evaluation of the heat and energy performance of a datacenter by a new efficiency index: Energy Usage Effectiveness Design - EUED
title_sort Evaluation of the heat and energy performance of a datacenter by a new efficiency index: Energy Usage Effectiveness Design - EUED
author Santos, Alexandre F.
author_facet Santos, Alexandre F.
Souza, Heraldo J. L. de
Gaspar, Pedro Dinis
author_role author
author2 Souza, Heraldo J. L. de
Gaspar, Pedro Dinis
author2_role author
author
dc.contributor.none.fl_str_mv uBibliorum
dc.contributor.author.fl_str_mv Santos, Alexandre F.
Souza, Heraldo J. L. de
Gaspar, Pedro Dinis
dc.subject.por.fl_str_mv Data Centers
PUE
EUED
Data Center Cooling
topic Data Centers
PUE
EUED
Data Center Cooling
description Data Centers are growing steadily worldwide and they are expected to continue on growing up to 53% in 2020. Due to this growth the energy efficiency in this type of building is essential. There are methodologies to measure this efficiency; one example is PUE (Power Usage Effectiveness). The unit suggested for measuring efficiency at the design stage would be the EUED (Energy Usage Efficiency Design) with this will be used data to use "free cooling" and adiabatic system in some cases, a comparison will be made only considering the equipment in the worst situation. It also uses the study of enthalpy utilization as a new methodology to obtain the results. By doing so, differences were found, between cities than 1.21% of São Paulo in relation to Curitiba and 10.61% of Rio de Janeiro in relation to Curitiba. The indices obtained by applying the EUED index were 1.245 kW.kW- 1 for Curitiba, 1.260 kW.kW-1 for São Paulo and 1.377 kW.kW-1 for Rio de Janeiro, respectively, giving a difference of 16.86% for Curitiba of 16.19% for São Paulo and 10.31% for Rio de Janeiro in relation to PUE COA (Power Usage Effectiveness Constant Outdoor Air).
publishDate 2019
dc.date.none.fl_str_mv 2019-11-06T11:33:59Z
2019
2019-01-01T00:00:00Z
dc.type.status.fl_str_mv info:eu-repo/semantics/publishedVersion
dc.type.driver.fl_str_mv info:eu-repo/semantics/article
format article
status_str publishedVersion
dc.identifier.uri.fl_str_mv http://hdl.handle.net/10400.6/7528
url http://hdl.handle.net/10400.6/7528
dc.language.iso.fl_str_mv eng
language eng
dc.relation.none.fl_str_mv 10.18462/iir.icr.2019.0885
dc.rights.driver.fl_str_mv info:eu-repo/semantics/openAccess
eu_rights_str_mv openAccess
dc.format.none.fl_str_mv application/pdf
dc.publisher.none.fl_str_mv The 25th IIR International Congress of Refrigeration (ICR 2019)
publisher.none.fl_str_mv The 25th IIR International Congress of Refrigeration (ICR 2019)
dc.source.none.fl_str_mv reponame:Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)
instname:Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informação
instacron:RCAAP
instname_str Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informação
instacron_str RCAAP
institution RCAAP
reponame_str Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)
collection Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)
repository.name.fl_str_mv Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos) - Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informação
repository.mail.fl_str_mv
_version_ 1799136374870245376