Influence of the test procedure for setting the external air movement on the thermal performance of open multideck display case

Detalhes bibliográficos
Autor(a) principal: Heidinger, Gustavo Galdi
Data de Publicação: 2014
Outros Autores: Nascimento, Samuel Mariano do, Gaspar, Pedro Dinis, Silva, Pedro Dinho da
Tipo de documento: Artigo
Idioma: eng
Título da fonte: Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)
Texto Completo: http://hdl.handle.net/10400.6/7235
Resumo: This paper reports the experimental results with an open multideck display case with dual air curtain. Manufacturers seek during the design phase of the equipment to certify its suitability to the testing standards with the lowest energy consumption and ensuring food safety. The testing standard ISO 23953 is usually followed to determine the equipment's thermal cooling load. However, some manufacturers use different procedures to set the external air velocity. The thermal cooling load will depend upon it. According to ISO 23953, the mean horizontal air velocity, with the refrigerated display case switched off, shall be 0.2 m/s. Thus, this paper reports the experimental results of tests where the initial procedure of setting the air velocity was performed by two different methods: (1) with the display case cooling on (2) and switched off as required by ISO 23953. The comparison of experimental results for the two conditions (switched off relatively to switched on) provide the quantitative variation of frost formation (-24%) and condensed water (+180%) on the evaporator coil and how this phenomena affects the distribution and magnitudes of air velocity (+7%); inlet (+5.9°C) and outlet temperatures (+5.5°C); the components of the total sensible (+10%) and latent (+15%) heat loads; and the average product temperatures (+176%). The analysis of experimental data provides the necessary basis to conclude that the initial procedure how the air movement is set affects significantly the performance of the equipment under testing. The results show that air movement procedure defined in the standard, although providing a higher thermal cooling load, is the most appropriated since the equipment will be able to operate correctly under more demanding ambient conditions and thus its design provides a better thermal performance.
id RCAP_4fbb0116b16de258a00973eb4967808a
oai_identifier_str oai:ubibliorum.ubi.pt:10400.6/7235
network_acronym_str RCAP
network_name_str Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)
repository_id_str 7160
spelling Influence of the test procedure for setting the external air movement on the thermal performance of open multideck display caseRefrigerationDisplay caseExperimental testingHeat loadsFrost formationAirflow distributionThis paper reports the experimental results with an open multideck display case with dual air curtain. Manufacturers seek during the design phase of the equipment to certify its suitability to the testing standards with the lowest energy consumption and ensuring food safety. The testing standard ISO 23953 is usually followed to determine the equipment's thermal cooling load. However, some manufacturers use different procedures to set the external air velocity. The thermal cooling load will depend upon it. According to ISO 23953, the mean horizontal air velocity, with the refrigerated display case switched off, shall be 0.2 m/s. Thus, this paper reports the experimental results of tests where the initial procedure of setting the air velocity was performed by two different methods: (1) with the display case cooling on (2) and switched off as required by ISO 23953. The comparison of experimental results for the two conditions (switched off relatively to switched on) provide the quantitative variation of frost formation (-24%) and condensed water (+180%) on the evaporator coil and how this phenomena affects the distribution and magnitudes of air velocity (+7%); inlet (+5.9°C) and outlet temperatures (+5.5°C); the components of the total sensible (+10%) and latent (+15%) heat loads; and the average product temperatures (+176%). The analysis of experimental data provides the necessary basis to conclude that the initial procedure how the air movement is set affects significantly the performance of the equipment under testing. The results show that air movement procedure defined in the standard, although providing a higher thermal cooling load, is the most appropriated since the equipment will be able to operate correctly under more demanding ambient conditions and thus its design provides a better thermal performance.WSEAS PressuBibliorumHeidinger, Gustavo GaldiNascimento, Samuel Mariano doGaspar, Pedro DinisSilva, Pedro Dinho da2019-10-11T10:23:58Z20142014-01-01T00:00:00Zinfo:eu-repo/semantics/publishedVersioninfo:eu-repo/semantics/articleapplication/pdfhttp://hdl.handle.net/10400.6/7235engHeidinger, Gustavo & Nascimento, S & Gaspar, Pedro & Silva, Pedro. (2014). Influence of the test procedure for setting the external air movement on the thermal performance of open multideck display case. 10.13140/2.1.1490.0166.978-960-474-402-2DOI: 10.13140/2.1.1490.0166info:eu-repo/semantics/openAccessreponame:Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)instname:Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informaçãoinstacron:RCAAP2023-12-15T09:46:27Zoai:ubibliorum.ubi.pt:10400.6/7235Portal AgregadorONGhttps://www.rcaap.pt/oai/openaireopendoar:71602024-03-20T00:47:48.023748Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos) - Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informaçãofalse
dc.title.none.fl_str_mv Influence of the test procedure for setting the external air movement on the thermal performance of open multideck display case
title Influence of the test procedure for setting the external air movement on the thermal performance of open multideck display case
spellingShingle Influence of the test procedure for setting the external air movement on the thermal performance of open multideck display case
Heidinger, Gustavo Galdi
Refrigeration
Display case
Experimental testing
Heat loads
Frost formation
Airflow distribution
title_short Influence of the test procedure for setting the external air movement on the thermal performance of open multideck display case
title_full Influence of the test procedure for setting the external air movement on the thermal performance of open multideck display case
title_fullStr Influence of the test procedure for setting the external air movement on the thermal performance of open multideck display case
title_full_unstemmed Influence of the test procedure for setting the external air movement on the thermal performance of open multideck display case
title_sort Influence of the test procedure for setting the external air movement on the thermal performance of open multideck display case
author Heidinger, Gustavo Galdi
author_facet Heidinger, Gustavo Galdi
Nascimento, Samuel Mariano do
Gaspar, Pedro Dinis
Silva, Pedro Dinho da
author_role author
author2 Nascimento, Samuel Mariano do
Gaspar, Pedro Dinis
Silva, Pedro Dinho da
author2_role author
author
author
dc.contributor.none.fl_str_mv uBibliorum
dc.contributor.author.fl_str_mv Heidinger, Gustavo Galdi
Nascimento, Samuel Mariano do
Gaspar, Pedro Dinis
Silva, Pedro Dinho da
dc.subject.por.fl_str_mv Refrigeration
Display case
Experimental testing
Heat loads
Frost formation
Airflow distribution
topic Refrigeration
Display case
Experimental testing
Heat loads
Frost formation
Airflow distribution
description This paper reports the experimental results with an open multideck display case with dual air curtain. Manufacturers seek during the design phase of the equipment to certify its suitability to the testing standards with the lowest energy consumption and ensuring food safety. The testing standard ISO 23953 is usually followed to determine the equipment's thermal cooling load. However, some manufacturers use different procedures to set the external air velocity. The thermal cooling load will depend upon it. According to ISO 23953, the mean horizontal air velocity, with the refrigerated display case switched off, shall be 0.2 m/s. Thus, this paper reports the experimental results of tests where the initial procedure of setting the air velocity was performed by two different methods: (1) with the display case cooling on (2) and switched off as required by ISO 23953. The comparison of experimental results for the two conditions (switched off relatively to switched on) provide the quantitative variation of frost formation (-24%) and condensed water (+180%) on the evaporator coil and how this phenomena affects the distribution and magnitudes of air velocity (+7%); inlet (+5.9°C) and outlet temperatures (+5.5°C); the components of the total sensible (+10%) and latent (+15%) heat loads; and the average product temperatures (+176%). The analysis of experimental data provides the necessary basis to conclude that the initial procedure how the air movement is set affects significantly the performance of the equipment under testing. The results show that air movement procedure defined in the standard, although providing a higher thermal cooling load, is the most appropriated since the equipment will be able to operate correctly under more demanding ambient conditions and thus its design provides a better thermal performance.
publishDate 2014
dc.date.none.fl_str_mv 2014
2014-01-01T00:00:00Z
2019-10-11T10:23:58Z
dc.type.status.fl_str_mv info:eu-repo/semantics/publishedVersion
dc.type.driver.fl_str_mv info:eu-repo/semantics/article
format article
status_str publishedVersion
dc.identifier.uri.fl_str_mv http://hdl.handle.net/10400.6/7235
url http://hdl.handle.net/10400.6/7235
dc.language.iso.fl_str_mv eng
language eng
dc.relation.none.fl_str_mv Heidinger, Gustavo & Nascimento, S & Gaspar, Pedro & Silva, Pedro. (2014). Influence of the test procedure for setting the external air movement on the thermal performance of open multideck display case. 10.13140/2.1.1490.0166.
978-960-474-402-2
DOI: 10.13140/2.1.1490.0166
dc.rights.driver.fl_str_mv info:eu-repo/semantics/openAccess
eu_rights_str_mv openAccess
dc.format.none.fl_str_mv application/pdf
dc.publisher.none.fl_str_mv WSEAS Press
publisher.none.fl_str_mv WSEAS Press
dc.source.none.fl_str_mv reponame:Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)
instname:Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informação
instacron:RCAAP
instname_str Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informação
instacron_str RCAAP
institution RCAAP
reponame_str Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)
collection Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)
repository.name.fl_str_mv Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos) - Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informação
repository.mail.fl_str_mv
_version_ 1799136372827619328