Experimental comparison between R409A and R437A performance in a heat pump unit
Autor(a) principal: | |
---|---|
Data de Publicação: | 2017 |
Outros Autores: | , , |
Tipo de documento: | Artigo |
Idioma: | eng |
Título da fonte: | Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos) |
Texto Completo: | http://hdl.handle.net/10400.6/7585 |
Resumo: | This paper reports an experimental comparison between the use of the refrigerants R409A and R437A in a heat pump unit designed and developed to work with R12. Although the use of both refrigerants in new equipments were abolished in EU and US according the new F-Gas Regulation of EU and SNAP, they still being used as options for R12 in old equipments, especially in developing countries. Both refrigerants were studied for the same test conditions, according to two groups of tests: group A (variation of the heat source temperature) and group B (variation of refrigerant flow rate). The results obtained showed that the R437A presents a higher discharge pressure and a lower discharge temperature. The heating and cooling capacities of both refrigerants were similar, as well as the exergetic efficiency. For the group A of tests the COP of both refrigerants was similar and for the group B of tests the R409A presented an average COP 15% higher. According to the results obtained it is recommended the use of R409A in old equipments (as transition refrigerant) until the acquisition of equipments operating with refrigerants with low-GWP becomes technically and economic feasible. |
id |
RCAP_ecf196947f3bd94016363088ef3bc1a5 |
---|---|
oai_identifier_str |
oai:ubibliorum.ubi.pt:10400.6/7585 |
network_acronym_str |
RCAP |
network_name_str |
Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos) |
repository_id_str |
7160 |
spelling |
Experimental comparison between R409A and R437A performance in a heat pump unitR409AR437AExergetic studyEnergetic performanceHeat pumpThis paper reports an experimental comparison between the use of the refrigerants R409A and R437A in a heat pump unit designed and developed to work with R12. Although the use of both refrigerants in new equipments were abolished in EU and US according the new F-Gas Regulation of EU and SNAP, they still being used as options for R12 in old equipments, especially in developing countries. Both refrigerants were studied for the same test conditions, according to two groups of tests: group A (variation of the heat source temperature) and group B (variation of refrigerant flow rate). The results obtained showed that the R437A presents a higher discharge pressure and a lower discharge temperature. The heating and cooling capacities of both refrigerants were similar, as well as the exergetic efficiency. For the group A of tests the COP of both refrigerants was similar and for the group B of tests the R409A presented an average COP 15% higher. According to the results obtained it is recommended the use of R409A in old equipments (as transition refrigerant) until the acquisition of equipments operating with refrigerants with low-GWP becomes technically and economic feasible.Open EngineeringuBibliorumDuarte, Miguel VicentePires, Luís Carlos CarvalhoSilva, Pedro Dinho daGaspar, Pedro Dinis2019-11-19T09:40:55Z20172017-01-01T00:00:00Zinfo:eu-repo/semantics/publishedVersioninfo:eu-repo/semantics/articleapplication/pdfhttp://hdl.handle.net/10400.6/7585eng10.1515/eng-2017-0011info:eu-repo/semantics/openAccessreponame:Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos)instname:Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informaçãoinstacron:RCAAP2023-12-15T09:47:04Zoai:ubibliorum.ubi.pt:10400.6/7585Portal AgregadorONGhttps://www.rcaap.pt/oai/openaireopendoar:71602024-03-20T00:48:04.556174Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos) - Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informaçãofalse |
dc.title.none.fl_str_mv |
Experimental comparison between R409A and R437A performance in a heat pump unit |
title |
Experimental comparison between R409A and R437A performance in a heat pump unit |
spellingShingle |
Experimental comparison between R409A and R437A performance in a heat pump unit Duarte, Miguel Vicente R409A R437A Exergetic study Energetic performance Heat pump |
title_short |
Experimental comparison between R409A and R437A performance in a heat pump unit |
title_full |
Experimental comparison between R409A and R437A performance in a heat pump unit |
title_fullStr |
Experimental comparison between R409A and R437A performance in a heat pump unit |
title_full_unstemmed |
Experimental comparison between R409A and R437A performance in a heat pump unit |
title_sort |
Experimental comparison between R409A and R437A performance in a heat pump unit |
author |
Duarte, Miguel Vicente |
author_facet |
Duarte, Miguel Vicente Pires, Luís Carlos Carvalho Silva, Pedro Dinho da Gaspar, Pedro Dinis |
author_role |
author |
author2 |
Pires, Luís Carlos Carvalho Silva, Pedro Dinho da Gaspar, Pedro Dinis |
author2_role |
author author author |
dc.contributor.none.fl_str_mv |
uBibliorum |
dc.contributor.author.fl_str_mv |
Duarte, Miguel Vicente Pires, Luís Carlos Carvalho Silva, Pedro Dinho da Gaspar, Pedro Dinis |
dc.subject.por.fl_str_mv |
R409A R437A Exergetic study Energetic performance Heat pump |
topic |
R409A R437A Exergetic study Energetic performance Heat pump |
description |
This paper reports an experimental comparison between the use of the refrigerants R409A and R437A in a heat pump unit designed and developed to work with R12. Although the use of both refrigerants in new equipments were abolished in EU and US according the new F-Gas Regulation of EU and SNAP, they still being used as options for R12 in old equipments, especially in developing countries. Both refrigerants were studied for the same test conditions, according to two groups of tests: group A (variation of the heat source temperature) and group B (variation of refrigerant flow rate). The results obtained showed that the R437A presents a higher discharge pressure and a lower discharge temperature. The heating and cooling capacities of both refrigerants were similar, as well as the exergetic efficiency. For the group A of tests the COP of both refrigerants was similar and for the group B of tests the R409A presented an average COP 15% higher. According to the results obtained it is recommended the use of R409A in old equipments (as transition refrigerant) until the acquisition of equipments operating with refrigerants with low-GWP becomes technically and economic feasible. |
publishDate |
2017 |
dc.date.none.fl_str_mv |
2017 2017-01-01T00:00:00Z 2019-11-19T09:40:55Z |
dc.type.status.fl_str_mv |
info:eu-repo/semantics/publishedVersion |
dc.type.driver.fl_str_mv |
info:eu-repo/semantics/article |
format |
article |
status_str |
publishedVersion |
dc.identifier.uri.fl_str_mv |
http://hdl.handle.net/10400.6/7585 |
url |
http://hdl.handle.net/10400.6/7585 |
dc.language.iso.fl_str_mv |
eng |
language |
eng |
dc.relation.none.fl_str_mv |
10.1515/eng-2017-0011 |
dc.rights.driver.fl_str_mv |
info:eu-repo/semantics/openAccess |
eu_rights_str_mv |
openAccess |
dc.format.none.fl_str_mv |
application/pdf |
dc.publisher.none.fl_str_mv |
Open Engineering |
publisher.none.fl_str_mv |
Open Engineering |
dc.source.none.fl_str_mv |
reponame:Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos) instname:Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informação instacron:RCAAP |
instname_str |
Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informação |
instacron_str |
RCAAP |
institution |
RCAAP |
reponame_str |
Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos) |
collection |
Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos) |
repository.name.fl_str_mv |
Repositório Científico de Acesso Aberto de Portugal (Repositórios Cientìficos) - Agência para a Sociedade do Conhecimento (UMIC) - FCT - Sociedade da Informação |
repository.mail.fl_str_mv |
|
_version_ |
1799136375431233536 |