Avaliação dos Impactos da Impedância de Falta e da Geração Distribuída em Estudos de Afundamentos de Tensão
Autor(a) principal: | |
---|---|
Data de Publicação: | 2009 |
Tipo de documento: | Dissertação |
Idioma: | por |
Título da fonte: | Repositório Institucional da UFG |
dARK ID: | ark:/38995/0013000003bwp |
Texto Completo: | http://repositorio.bc.ufg.br/tede/handle/tde/988 |
Resumo: | This work presents an impact analysis of the fault impedance and distributed ge- neration on the amplitude and annual average quantity of voltage sags in sensitive end-users. Phase-to-ground solid and non-solid faults were simulated in 62 transmission lines at 230, 138, 69 and 13.8 kV, which made part of the electrical system of the municipality of Goiânia, the capital city of the Goiás State, Brazil. For each fault position, a resistive fault impedance was considered. This impedance was considered equal to 0, 2, 5, 10, or 15  or even random. In this case, each one of the mentioned impedance values has a specific probability to occur. The voltage-behind-reactance synchronous machine model was used to model the distributed generation units. The analysis here described is based on simulation results obtained through the Fault Position Method in combination with the Monte Carlo Method. The faults were si-mulated through a frequency-domain fault simulation software called ANAFAS. In order to overcome some limitations and increase the flexibility of the simulation tool, a computational program, called ANAFAS-GUI, was developed in Java language. This program allows the automatic simulation of several cases, with different fault characteristics, by running ANAFAS in background mode. The Monte Carlo Method was implemented in MATLAB. Thus, an efficient computational tool has resulted from the combination of the developed computational tools for the purposes of this work. The main simulation results are the tenden-cy and probability density curves of the voltage sags and their classes. From the results it can be concluded that, if the fault impedance is considered as being a random variable, then the predict voltage sags quantity and severity at the sensitive end-user bus are more accurate when compared to the cases in which this impedance is not considered as such. It can also be concluded that, the connection of a distributed generation unit next to the sensitive end-user bus may result in a decreasing of the voltage sags quantity and severity at this bus, depending on the rated power of the unit |
id |
UFG-2_543f8ec27d9a2e253e8448ce1dd95b2e |
---|---|
oai_identifier_str |
oai:repositorio.bc.ufg.br:tde/988 |
network_acronym_str |
UFG-2 |
network_name_str |
Repositório Institucional da UFG |
repository_id_str |
|
spelling |
ALVARENGA, Bernardo Pinheiro dehttp://lattes.cnpq.br/9850449311607643LEBORGNE, Roberto Chouhyhttp://lattes.cnpq.br/3938003534716565http://lattes.cnpq.br/2763790305104492RAMOS, Alessandro Candido Lopes2014-07-29T15:08:21Z2009-12-142009-09-21RAMOS, Alessandro Candido Lopes. Impact Assessment of Fault Impedance and Distributed Generation Studies of Voltage Sags. 2009. 196 f. Dissertação (Mestrado em Engenharia) - Universidade Federal de Goiás, Goiânia, 2009.http://repositorio.bc.ufg.br/tede/handle/tde/988ark:/38995/0013000003bwpThis work presents an impact analysis of the fault impedance and distributed ge- neration on the amplitude and annual average quantity of voltage sags in sensitive end-users. Phase-to-ground solid and non-solid faults were simulated in 62 transmission lines at 230, 138, 69 and 13.8 kV, which made part of the electrical system of the municipality of Goiânia, the capital city of the Goiás State, Brazil. For each fault position, a resistive fault impedance was considered. This impedance was considered equal to 0, 2, 5, 10, or 15  or even random. In this case, each one of the mentioned impedance values has a specific probability to occur. The voltage-behind-reactance synchronous machine model was used to model the distributed generation units. The analysis here described is based on simulation results obtained through the Fault Position Method in combination with the Monte Carlo Method. The faults were si-mulated through a frequency-domain fault simulation software called ANAFAS. In order to overcome some limitations and increase the flexibility of the simulation tool, a computational program, called ANAFAS-GUI, was developed in Java language. This program allows the automatic simulation of several cases, with different fault characteristics, by running ANAFAS in background mode. The Monte Carlo Method was implemented in MATLAB. Thus, an efficient computational tool has resulted from the combination of the developed computational tools for the purposes of this work. The main simulation results are the tenden-cy and probability density curves of the voltage sags and their classes. From the results it can be concluded that, if the fault impedance is considered as being a random variable, then the predict voltage sags quantity and severity at the sensitive end-user bus are more accurate when compared to the cases in which this impedance is not considered as such. It can also be concluded that, the connection of a distributed generation unit next to the sensitive end-user bus may result in a decreasing of the voltage sags quantity and severity at this bus, depending on the rated power of the unitEste trabalho apresenta os impactos da impedância de falta e da geração distribuí-da na amplitude e quantidade média anual de afundamentos de tensão em consumidores sen-síveis. Foram simuladas faltas fase-terra sólidas e não sólidas em 62 linhas de 230, 138, 69 e 13,8 kV, as quais fazem parte do sistema elétrico do município de Goiânia, capital do Estado de Goiás, Brasil. Para cada posição de falta, uma impedância de falta resistiva foi considera-da. Esta impedância foi considerada igual a 0, 2, 5, 10 ou 15 Ω, ou mesmo aleatória. Neste caso, cada um dos valores de impedância mencionados tem uma probabilidade específica de ocorrer. O modelo de gerador síncrono fonte de tensão atrás de uma reatância , foi utilizado para a modelagem das unidades de geração distribuída. A análise descrita aquí é baseada em resultados de simulação obtidos através da combinação do Método das Posições de Falta e o Método de Monte Carlo. As faltas foram simuladas através de um software de simulação de faltas no domínio da frequência chamado ANAFAS. Visando eliminar algumas limitações e aumentar a flexibilidade deste software, um programa computacional, chamado ANAFAS-GUI, foi desenvolvido em linguagem JAVA. Este programa permite a simulação automática de diversos casos, com diferentes características de faltas, pela execução do ANAFAS em modo background. O método de Monte Carlo foi implementado em MATLAB. Assim, uma eficiênte ferramenta computacional resultou da combinação da ferramenta computacional desenvolvida e a ferramenta utilizada neste trabalho. Os resultados de simulação são apresen-tados através das curvas de tendência e de densidade de probabilidade dos afundamentos e de suas classes. A partir dos resultados pode-se concluir que, se a impedância de falta é conside-rada como sendo uma variável aleatória, então a quantidade e severidade dos afundamentos de tensão previstos em barras de consumidores sensíveis serão mais precisos quando compa-rados com os casos no qual esta impedância não é considerada como tal. Também pode ser concluído que, a conexão de unidades de geração distribuída próxima a barra de consumido-res sensíveis pode resultar em um decréscimo da quantidade e severidade dos afundamentos de tensão nesta barra, dependendo da potência nominal da unidadeMade available in DSpace on 2014-07-29T15:08:21Z (GMT). No. of bitstreams: 1 dissertacao alessandro ramos.pdf: 3510857 bytes, checksum: 4f913faa66790fd0df082b0105f19a77 (MD5) Previous issue date: 2009-09-21application/pdfhttp://repositorio.bc.ufg.br/TEDE/retrieve/3460/dissertacao%20alessandro%20ramos.pdf.jpgporUniversidade Federal de GoiásMestrado em Engenharia Elétrica e de ComputaçãoUFGBREngenhariaafundamentos de tensão, impedância de falta, geração distribuídavoltage sags, impedance fault, distributed generationCNPQ::ENGENHARIAS::ENGENHARIA ELETRICAAvaliação dos Impactos da Impedância de Falta e da Geração Distribuída em Estudos de Afundamentos de TensãoImpact Assessment of Fault Impedance and Distributed Generation Studies of Voltage Sagsinfo:eu-repo/semantics/publishedVersioninfo:eu-repo/semantics/masterThesisinfo:eu-repo/semantics/openAccessreponame:Repositório Institucional da UFGinstname:Universidade Federal de Goiás (UFG)instacron:UFGORIGINALdissertacao alessandro ramos.pdfapplication/pdf3510857http://repositorio.bc.ufg.br/tede/bitstreams/a91fcb97-f054-4a7e-8564-4a2036019ee4/download4f913faa66790fd0df082b0105f19a77MD51THUMBNAILdissertacao alessandro ramos.pdf.jpgdissertacao alessandro ramos.pdf.jpgGenerated Thumbnailimage/jpeg2238http://repositorio.bc.ufg.br/tede/bitstreams/df40d54e-7926-4363-9fb1-4491ac1c6875/downloadac37d69c416d3717df9ed2aeb26d45b6MD52tde/9882014-07-30 03:05:39.932open.accessoai:repositorio.bc.ufg.br:tde/988http://repositorio.bc.ufg.br/tedeRepositório InstitucionalPUBhttp://repositorio.bc.ufg.br/oai/requesttasesdissertacoes.bc@ufg.bropendoar:2014-07-30T06:05:39Repositório Institucional da UFG - Universidade Federal de Goiás (UFG)false |
dc.title.por.fl_str_mv |
Avaliação dos Impactos da Impedância de Falta e da Geração Distribuída em Estudos de Afundamentos de Tensão |
dc.title.alternative.eng.fl_str_mv |
Impact Assessment of Fault Impedance and Distributed Generation Studies of Voltage Sags |
title |
Avaliação dos Impactos da Impedância de Falta e da Geração Distribuída em Estudos de Afundamentos de Tensão |
spellingShingle |
Avaliação dos Impactos da Impedância de Falta e da Geração Distribuída em Estudos de Afundamentos de Tensão RAMOS, Alessandro Candido Lopes afundamentos de tensão, impedância de falta, geração distribuída voltage sags, impedance fault, distributed generation CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA |
title_short |
Avaliação dos Impactos da Impedância de Falta e da Geração Distribuída em Estudos de Afundamentos de Tensão |
title_full |
Avaliação dos Impactos da Impedância de Falta e da Geração Distribuída em Estudos de Afundamentos de Tensão |
title_fullStr |
Avaliação dos Impactos da Impedância de Falta e da Geração Distribuída em Estudos de Afundamentos de Tensão |
title_full_unstemmed |
Avaliação dos Impactos da Impedância de Falta e da Geração Distribuída em Estudos de Afundamentos de Tensão |
title_sort |
Avaliação dos Impactos da Impedância de Falta e da Geração Distribuída em Estudos de Afundamentos de Tensão |
author |
RAMOS, Alessandro Candido Lopes |
author_facet |
RAMOS, Alessandro Candido Lopes |
author_role |
author |
dc.contributor.advisor1.fl_str_mv |
ALVARENGA, Bernardo Pinheiro de |
dc.contributor.advisor1Lattes.fl_str_mv |
http://lattes.cnpq.br/9850449311607643 |
dc.contributor.advisor-co1.fl_str_mv |
LEBORGNE, Roberto Chouhy |
dc.contributor.advisor-co1Lattes.fl_str_mv |
http://lattes.cnpq.br/3938003534716565 |
dc.contributor.authorLattes.fl_str_mv |
http://lattes.cnpq.br/2763790305104492 |
dc.contributor.author.fl_str_mv |
RAMOS, Alessandro Candido Lopes |
contributor_str_mv |
ALVARENGA, Bernardo Pinheiro de LEBORGNE, Roberto Chouhy |
dc.subject.por.fl_str_mv |
afundamentos de tensão, impedância de falta, geração distribuída |
topic |
afundamentos de tensão, impedância de falta, geração distribuída voltage sags, impedance fault, distributed generation CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA |
dc.subject.eng.fl_str_mv |
voltage sags, impedance fault, distributed generation |
dc.subject.cnpq.fl_str_mv |
CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA |
description |
This work presents an impact analysis of the fault impedance and distributed ge- neration on the amplitude and annual average quantity of voltage sags in sensitive end-users. Phase-to-ground solid and non-solid faults were simulated in 62 transmission lines at 230, 138, 69 and 13.8 kV, which made part of the electrical system of the municipality of Goiânia, the capital city of the Goiás State, Brazil. For each fault position, a resistive fault impedance was considered. This impedance was considered equal to 0, 2, 5, 10, or 15  or even random. In this case, each one of the mentioned impedance values has a specific probability to occur. The voltage-behind-reactance synchronous machine model was used to model the distributed generation units. The analysis here described is based on simulation results obtained through the Fault Position Method in combination with the Monte Carlo Method. The faults were si-mulated through a frequency-domain fault simulation software called ANAFAS. In order to overcome some limitations and increase the flexibility of the simulation tool, a computational program, called ANAFAS-GUI, was developed in Java language. This program allows the automatic simulation of several cases, with different fault characteristics, by running ANAFAS in background mode. The Monte Carlo Method was implemented in MATLAB. Thus, an efficient computational tool has resulted from the combination of the developed computational tools for the purposes of this work. The main simulation results are the tenden-cy and probability density curves of the voltage sags and their classes. From the results it can be concluded that, if the fault impedance is considered as being a random variable, then the predict voltage sags quantity and severity at the sensitive end-user bus are more accurate when compared to the cases in which this impedance is not considered as such. It can also be concluded that, the connection of a distributed generation unit next to the sensitive end-user bus may result in a decreasing of the voltage sags quantity and severity at this bus, depending on the rated power of the unit |
publishDate |
2009 |
dc.date.available.fl_str_mv |
2009-12-14 |
dc.date.issued.fl_str_mv |
2009-09-21 |
dc.date.accessioned.fl_str_mv |
2014-07-29T15:08:21Z |
dc.type.status.fl_str_mv |
info:eu-repo/semantics/publishedVersion |
dc.type.driver.fl_str_mv |
info:eu-repo/semantics/masterThesis |
format |
masterThesis |
status_str |
publishedVersion |
dc.identifier.citation.fl_str_mv |
RAMOS, Alessandro Candido Lopes. Impact Assessment of Fault Impedance and Distributed Generation Studies of Voltage Sags. 2009. 196 f. Dissertação (Mestrado em Engenharia) - Universidade Federal de Goiás, Goiânia, 2009. |
dc.identifier.uri.fl_str_mv |
http://repositorio.bc.ufg.br/tede/handle/tde/988 |
dc.identifier.dark.fl_str_mv |
ark:/38995/0013000003bwp |
identifier_str_mv |
RAMOS, Alessandro Candido Lopes. Impact Assessment of Fault Impedance and Distributed Generation Studies of Voltage Sags. 2009. 196 f. Dissertação (Mestrado em Engenharia) - Universidade Federal de Goiás, Goiânia, 2009. ark:/38995/0013000003bwp |
url |
http://repositorio.bc.ufg.br/tede/handle/tde/988 |
dc.language.iso.fl_str_mv |
por |
language |
por |
dc.rights.driver.fl_str_mv |
info:eu-repo/semantics/openAccess |
eu_rights_str_mv |
openAccess |
dc.format.none.fl_str_mv |
application/pdf |
dc.publisher.none.fl_str_mv |
Universidade Federal de Goiás |
dc.publisher.program.fl_str_mv |
Mestrado em Engenharia Elétrica e de Computação |
dc.publisher.initials.fl_str_mv |
UFG |
dc.publisher.country.fl_str_mv |
BR |
dc.publisher.department.fl_str_mv |
Engenharia |
publisher.none.fl_str_mv |
Universidade Federal de Goiás |
dc.source.none.fl_str_mv |
reponame:Repositório Institucional da UFG instname:Universidade Federal de Goiás (UFG) instacron:UFG |
instname_str |
Universidade Federal de Goiás (UFG) |
instacron_str |
UFG |
institution |
UFG |
reponame_str |
Repositório Institucional da UFG |
collection |
Repositório Institucional da UFG |
bitstream.url.fl_str_mv |
http://repositorio.bc.ufg.br/tede/bitstreams/a91fcb97-f054-4a7e-8564-4a2036019ee4/download http://repositorio.bc.ufg.br/tede/bitstreams/df40d54e-7926-4363-9fb1-4491ac1c6875/download |
bitstream.checksum.fl_str_mv |
4f913faa66790fd0df082b0105f19a77 ac37d69c416d3717df9ed2aeb26d45b6 |
bitstream.checksumAlgorithm.fl_str_mv |
MD5 MD5 |
repository.name.fl_str_mv |
Repositório Institucional da UFG - Universidade Federal de Goiás (UFG) |
repository.mail.fl_str_mv |
tasesdissertacoes.bc@ufg.br |
_version_ |
1815172544867598336 |