Avaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de caso

Detalhes bibliográficos
Autor(a) principal: Silva, Jéssica Cristina Marques da
Data de Publicação: 2020
Tipo de documento: Dissertação
Idioma: por
Título da fonte: Repositório Institucional da UFG
Texto Completo: http://repositorio.bc.ufg.br/tede/handle/tede/11035
Resumo: Approximately 20% of the transmission lines of the Brazilian national interconnected system are double circuit, being the most used configuration type after single circuit transmission lines. For this reason, the importance of studying double circuit transmission lines is highlighted. When two transmission lines are close, such as a double circuit transmission line, a mutual zero sequence coupling is observed between them. This mutual zero sequence coupling interferes in the impedance calculated by the distance protection, in the case of short circuits involving the ground, due to the zero sequence current in the healthy parallel line and the presence of zero sequence mutual impedance. Considering the distance protection applied to double circuit transmission lines, this dissertation presents a comparative assessment between traditional and compensated distance protections, which considers the influence of the operating condition of the parallel circuit on the protected line. In addition, the distance protections are assessed using phase comparators, such that in the results the impedance units operation is analyzed. For this purpose, a 138 kV real transmission system is modeled in the Alternative Transient Program (ATP) software and subjected to single phase-to-ground fault, varying the fault resistance value, the system loading, the power of the sources, the fault line and the fault location in each line. From the results obtained, it is verified that the correction of the mutual zero sequence coupling can improve or worsen the performance of the distance protection in relation to the function 21 traditional, which depends on power of the sources and the fault location. Thus, it is emphasized that for the cases analysed the correction of the mutual zero sequence coupling does not significantly improved the performance of the distance protection.
id UFG-2_8f5b5cbb928e6477d56e5b25c95c19ff
oai_identifier_str oai:repositorio.bc.ufg.br:tede/11035
network_acronym_str UFG-2
network_name_str Repositório Institucional da UFG
repository_id_str
spelling Almeida, Maria Leonor Silva dehttp://lattes.cnpq.br/7955955842189669Lopes, Felipe VigolvinoKopcak, IgorAlmeida, Maria Leonor Silva dehttp://lattes.cnpq.br/9727333894324895Silva, Jéssica Cristina Marques da2021-01-15T15:57:45Z2021-01-15T15:57:45Z2020-10-30SILVA, J. C. M. Avaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de caso. 2020. 84 f. Dissertação (Mestrado em Engenharia Elétrica e da Computação) - Universidade Federal de Goiás, Goiânia, 2020.http://repositorio.bc.ufg.br/tede/handle/tede/11035ark:/38995/00130000052ddApproximately 20% of the transmission lines of the Brazilian national interconnected system are double circuit, being the most used configuration type after single circuit transmission lines. For this reason, the importance of studying double circuit transmission lines is highlighted. When two transmission lines are close, such as a double circuit transmission line, a mutual zero sequence coupling is observed between them. This mutual zero sequence coupling interferes in the impedance calculated by the distance protection, in the case of short circuits involving the ground, due to the zero sequence current in the healthy parallel line and the presence of zero sequence mutual impedance. Considering the distance protection applied to double circuit transmission lines, this dissertation presents a comparative assessment between traditional and compensated distance protections, which considers the influence of the operating condition of the parallel circuit on the protected line. In addition, the distance protections are assessed using phase comparators, such that in the results the impedance units operation is analyzed. For this purpose, a 138 kV real transmission system is modeled in the Alternative Transient Program (ATP) software and subjected to single phase-to-ground fault, varying the fault resistance value, the system loading, the power of the sources, the fault line and the fault location in each line. From the results obtained, it is verified that the correction of the mutual zero sequence coupling can improve or worsen the performance of the distance protection in relation to the function 21 traditional, which depends on power of the sources and the fault location. Thus, it is emphasized that for the cases analysed the correction of the mutual zero sequence coupling does not significantly improved the performance of the distance protection.Aproximadamente 20% das linhas de transmissão do Sistema Interligado Nacional brasileiro são de circuito duplo, sendo o tipo de configuração mais utilizada após as linhas de transmissão de circuito simples. Por esse motivo, destaca-se a importância de estudos INTERNAL relacionados a esse tipo de arranjo de linhas de transmissão. Quando duas linhas de transmissão estão próximas, por exemplo uma linha de transmissão de circuito duplo, observa-se um acoplamento mútuo de sequência zero entre elas. Esse acoplamento mútuo de sequência zero interfere no cálculo da impedância determinada pelo relé de distância, no caso de curtos-circuitos que envolvam o terra, em função da corrente de sequência zero na linha paralela sã e da presença de impedância mútua de sequência zero. Considerando a proteção de distância aplicada a linhas de transmissão de circuito duplo, apresenta-se nesta dissertação uma avaliação comparativa entre as proteções de distância tradicional e compensada, a qual considera a influência da condição operativa do circuito paralelo à linha protegida. No mais, as proteções de distância são avaliadas por meio de comparadores de fase, tal que nos resultados é analisada a atuação das unidades de impedância. Para tanto, dois sistemas de sub-transmissão de 138 kV, implementados com base em dados reais, foram modelados no software Alternative Transient Program (ATP) e submetidos a diferentes curtos-circuitos monofásicos, variando-se o valor da resistência de falta, o carregamento do sistema, a força das fontes, a linha em falta e o local de aplicação do curto-circuito em cada linha. Dos resultados obtidos, verifica-se que a correção do acoplamento mútuo de sequência zero pode melhorar ou piorar o desempenho da proteção de distância em relação a função 21 tradicional, a depender da força das fontes e da localização de falta. Assim, ressalta-se que para os casos analisados a correção do acoplamento mútuo de sequência zero não apresentou melhorias significativas no desempenho da proteção de distância.Submitted by Luciana Ferreira (lucgeral@gmail.com) on 2021-01-15T11:52:42Z No. of bitstreams: 2 license_rdf: 805 bytes, checksum: 4460e5956bc1d1639be9ae6146a50347 (MD5) Dissertação - Jéssica Cristina Marques da Silva - 2020.pdf: 1980812 bytes, checksum: d778d28150c6fe565bcf2cc20dc542f2 (MD5)Approved for entry into archive by Luciana Ferreira (lucgeral@gmail.com) on 2021-01-15T15:57:45Z (GMT) No. of bitstreams: 2 license_rdf: 805 bytes, checksum: 4460e5956bc1d1639be9ae6146a50347 (MD5) Dissertação - Jéssica Cristina Marques da Silva - 2020.pdf: 1980812 bytes, checksum: d778d28150c6fe565bcf2cc20dc542f2 (MD5)Made available in DSpace on 2021-01-15T15:57:45Z (GMT). No. of bitstreams: 2 license_rdf: 805 bytes, checksum: 4460e5956bc1d1639be9ae6146a50347 (MD5) Dissertação - Jéssica Cristina Marques da Silva - 2020.pdf: 1980812 bytes, checksum: d778d28150c6fe565bcf2cc20dc542f2 (MD5) Previous issue date: 2020-10-30porUniversidade Federal de GoiásPrograma de Pós-graduação em Engenharia Elétrica e da Computação (EMC)UFGBrasilEscola de Engenharia Elétrica, Mecânica e de Computação - EMC (RG)Attribution-NonCommercial-NoDerivatives 4.0 Internationalhttp://creativecommons.org/licenses/by-nc-nd/4.0/info:eu-repo/semantics/openAccessLinhas de transmissão de circuito duploLinhas de transmissão de circuito simplesProteção de distânciaAcoplamento mútuo de sequência zeroDouble circuit transmission linesSingle circuit transmission linesDistance ProtectionMutual zeroSequence couplingENGENHARIAS::ENGENHARIA ELETRICA::CIRCUITOS ELETRICOS, MAGNETICOS E ELETRONICOSAvaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de casoDistance protection in double-circuit transmission lines assessment with case studyinfo:eu-repo/semantics/publishedVersioninfo:eu-repo/semantics/masterThesis475005005004435reponame:Repositório Institucional da UFGinstname:Universidade Federal de Goiás (UFG)instacron:UFGLICENSElicense.txtlicense.txttext/plain; charset=utf-81748http://repositorio.bc.ufg.br/tede/bitstreams/ece18d35-ac1d-4beb-8126-29a4b06b9207/download8a4605be74aa9ea9d79846c1fba20a33MD51CC-LICENSElicense_rdflicense_rdfapplication/rdf+xml; charset=utf-8805http://repositorio.bc.ufg.br/tede/bitstreams/9caee657-193c-40b4-ab0b-afb612fe038a/download4460e5956bc1d1639be9ae6146a50347MD52ORIGINALDissertação - Jéssica Cristina Marques da Silva - 2020.pdfDissertação - Jéssica Cristina Marques da Silva - 2020.pdfapplication/pdf1980812http://repositorio.bc.ufg.br/tede/bitstreams/47b39444-6aa2-44bf-8c81-27257fb4c8c8/downloadd778d28150c6fe565bcf2cc20dc542f2MD53tede/110352021-01-15 12:57:45.838http://creativecommons.org/licenses/by-nc-nd/4.0/Attribution-NonCommercial-NoDerivatives 4.0 Internationalopen.accessoai:repositorio.bc.ufg.br:tede/11035http://repositorio.bc.ufg.br/tedeRepositório InstitucionalPUBhttp://repositorio.bc.ufg.br/oai/requesttasesdissertacoes.bc@ufg.bropendoar:2021-01-15T15:57:45Repositório Institucional da UFG - Universidade Federal de Goiás (UFG)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
dc.title.pt_BR.fl_str_mv Avaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de caso
dc.title.alternative.eng.fl_str_mv Distance protection in double-circuit transmission lines assessment with case study
title Avaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de caso
spellingShingle Avaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de caso
Silva, Jéssica Cristina Marques da
Linhas de transmissão de circuito duplo
Linhas de transmissão de circuito simples
Proteção de distância
Acoplamento mútuo de sequência zero
Double circuit transmission lines
Single circuit transmission lines
Distance Protection
Mutual zero
Sequence coupling
ENGENHARIAS::ENGENHARIA ELETRICA::CIRCUITOS ELETRICOS, MAGNETICOS E ELETRONICOS
title_short Avaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de caso
title_full Avaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de caso
title_fullStr Avaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de caso
title_full_unstemmed Avaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de caso
title_sort Avaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de caso
author Silva, Jéssica Cristina Marques da
author_facet Silva, Jéssica Cristina Marques da
author_role author
dc.contributor.advisor1.fl_str_mv Almeida, Maria Leonor Silva de
dc.contributor.advisor1Lattes.fl_str_mv http://lattes.cnpq.br/7955955842189669
dc.contributor.referee1.fl_str_mv Lopes, Felipe Vigolvino
dc.contributor.referee2.fl_str_mv Kopcak, Igor
dc.contributor.referee3.fl_str_mv Almeida, Maria Leonor Silva de
dc.contributor.authorLattes.fl_str_mv http://lattes.cnpq.br/9727333894324895
dc.contributor.author.fl_str_mv Silva, Jéssica Cristina Marques da
contributor_str_mv Almeida, Maria Leonor Silva de
Lopes, Felipe Vigolvino
Kopcak, Igor
Almeida, Maria Leonor Silva de
dc.subject.por.fl_str_mv Linhas de transmissão de circuito duplo
Linhas de transmissão de circuito simples
Proteção de distância
Acoplamento mútuo de sequência zero
topic Linhas de transmissão de circuito duplo
Linhas de transmissão de circuito simples
Proteção de distância
Acoplamento mútuo de sequência zero
Double circuit transmission lines
Single circuit transmission lines
Distance Protection
Mutual zero
Sequence coupling
ENGENHARIAS::ENGENHARIA ELETRICA::CIRCUITOS ELETRICOS, MAGNETICOS E ELETRONICOS
dc.subject.eng.fl_str_mv Double circuit transmission lines
Single circuit transmission lines
Distance Protection
Mutual zero
Sequence coupling
dc.subject.cnpq.fl_str_mv ENGENHARIAS::ENGENHARIA ELETRICA::CIRCUITOS ELETRICOS, MAGNETICOS E ELETRONICOS
description Approximately 20% of the transmission lines of the Brazilian national interconnected system are double circuit, being the most used configuration type after single circuit transmission lines. For this reason, the importance of studying double circuit transmission lines is highlighted. When two transmission lines are close, such as a double circuit transmission line, a mutual zero sequence coupling is observed between them. This mutual zero sequence coupling interferes in the impedance calculated by the distance protection, in the case of short circuits involving the ground, due to the zero sequence current in the healthy parallel line and the presence of zero sequence mutual impedance. Considering the distance protection applied to double circuit transmission lines, this dissertation presents a comparative assessment between traditional and compensated distance protections, which considers the influence of the operating condition of the parallel circuit on the protected line. In addition, the distance protections are assessed using phase comparators, such that in the results the impedance units operation is analyzed. For this purpose, a 138 kV real transmission system is modeled in the Alternative Transient Program (ATP) software and subjected to single phase-to-ground fault, varying the fault resistance value, the system loading, the power of the sources, the fault line and the fault location in each line. From the results obtained, it is verified that the correction of the mutual zero sequence coupling can improve or worsen the performance of the distance protection in relation to the function 21 traditional, which depends on power of the sources and the fault location. Thus, it is emphasized that for the cases analysed the correction of the mutual zero sequence coupling does not significantly improved the performance of the distance protection.
publishDate 2020
dc.date.issued.fl_str_mv 2020-10-30
dc.date.accessioned.fl_str_mv 2021-01-15T15:57:45Z
dc.date.available.fl_str_mv 2021-01-15T15:57:45Z
dc.type.status.fl_str_mv info:eu-repo/semantics/publishedVersion
dc.type.driver.fl_str_mv info:eu-repo/semantics/masterThesis
format masterThesis
status_str publishedVersion
dc.identifier.citation.fl_str_mv SILVA, J. C. M. Avaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de caso. 2020. 84 f. Dissertação (Mestrado em Engenharia Elétrica e da Computação) - Universidade Federal de Goiás, Goiânia, 2020.
dc.identifier.uri.fl_str_mv http://repositorio.bc.ufg.br/tede/handle/tede/11035
dc.identifier.dark.fl_str_mv ark:/38995/00130000052dd
identifier_str_mv SILVA, J. C. M. Avaliação da proteção de distância em linhas de transmissão de circuito duplo com estudo de caso. 2020. 84 f. Dissertação (Mestrado em Engenharia Elétrica e da Computação) - Universidade Federal de Goiás, Goiânia, 2020.
ark:/38995/00130000052dd
url http://repositorio.bc.ufg.br/tede/handle/tede/11035
dc.language.iso.fl_str_mv por
language por
dc.relation.program.fl_str_mv 47
dc.relation.confidence.fl_str_mv 500
500
500
dc.relation.department.fl_str_mv 4
dc.relation.cnpq.fl_str_mv 435
dc.rights.driver.fl_str_mv Attribution-NonCommercial-NoDerivatives 4.0 International
http://creativecommons.org/licenses/by-nc-nd/4.0/
info:eu-repo/semantics/openAccess
rights_invalid_str_mv Attribution-NonCommercial-NoDerivatives 4.0 International
http://creativecommons.org/licenses/by-nc-nd/4.0/
eu_rights_str_mv openAccess
dc.publisher.none.fl_str_mv Universidade Federal de Goiás
dc.publisher.program.fl_str_mv Programa de Pós-graduação em Engenharia Elétrica e da Computação (EMC)
dc.publisher.initials.fl_str_mv UFG
dc.publisher.country.fl_str_mv Brasil
dc.publisher.department.fl_str_mv Escola de Engenharia Elétrica, Mecânica e de Computação - EMC (RG)
publisher.none.fl_str_mv Universidade Federal de Goiás
dc.source.none.fl_str_mv reponame:Repositório Institucional da UFG
instname:Universidade Federal de Goiás (UFG)
instacron:UFG
instname_str Universidade Federal de Goiás (UFG)
instacron_str UFG
institution UFG
reponame_str Repositório Institucional da UFG
collection Repositório Institucional da UFG
bitstream.url.fl_str_mv http://repositorio.bc.ufg.br/tede/bitstreams/ece18d35-ac1d-4beb-8126-29a4b06b9207/download
http://repositorio.bc.ufg.br/tede/bitstreams/9caee657-193c-40b4-ab0b-afb612fe038a/download
http://repositorio.bc.ufg.br/tede/bitstreams/47b39444-6aa2-44bf-8c81-27257fb4c8c8/download
bitstream.checksum.fl_str_mv 8a4605be74aa9ea9d79846c1fba20a33
4460e5956bc1d1639be9ae6146a50347
d778d28150c6fe565bcf2cc20dc542f2
bitstream.checksumAlgorithm.fl_str_mv MD5
MD5
MD5
repository.name.fl_str_mv Repositório Institucional da UFG - Universidade Federal de Goiás (UFG)
repository.mail.fl_str_mv tasesdissertacoes.bc@ufg.br
_version_ 1811721394576162816