Análise de atuação indevida do ERAC em desenergização de subestação, influenciada pela desaceleração de motores e proposta de lógica utilizando a função ANSI 81U com dois estágios de tensão de bloqueio e temporização

Detalhes bibliográficos
Autor(a) principal: Borges, Adriano
Data de Publicação: 2020
Tipo de documento: Dissertação
Idioma: por
Título da fonte: Repositório Institucional Manancial UFSM
Texto Completo: http://repositorio.ufsm.br/handle/1/22627
Resumo: The stability of the SEP is a major concern for System Operators worldwide. Several actions and controls are taken when a major disturbance occurs, with the aim of finding a new balance point, minimizing the disconnection of loads and avoiding generalized blackouts. One of the most important controls is the Under Frequency Load Shedding (UFLS), in Brazil called the Regional Load Relief Scheme (ERAC). This function has already avoided several blackouts with selective load cuts by underfrequency, bringing the system to the load-generation balance. ERAC’s performance is important for the stability of the National Interconnected System (SIN), however, the improper performance of this function generates problems for concessionaires, such as customer dissatisfaction and fines imposed by the National Electric Energy Agency - ANEEL. Following this reasoning, this paper analyzes the reliability of the ERAC system in SIN disturbances and some undue actions, influenced by the deceleration of induction motors. Then, the characteristic of the voltage wave that arises due to the influence of the motors is analyzed, with the aid of the DIgSILENT software, as well as which are the ideal settings for commercial underfrequency relays in the South region. This analysis was aided by the ANATEM software, by oscillographic records of actual actions by the SIN and undue actions by the RGE concessionaire underfrequency relays. Finally, a new ERAC schemes is proposed, obtained from two settings for the blocking voltage. As result, there is the blocking of the ANSI 81U function during engine the deceleration and the guarantee of the correct performance of the ERAC when it is requested.
id UFSM-20_853d1f6b95185a3a1853fbe1bdecfc60
oai_identifier_str oai:repositorio.ufsm.br:1/22627
network_acronym_str UFSM-20
network_name_str Repositório Institucional Manancial UFSM
repository_id_str 3913
spelling 2021-10-27T11:31:45Z2021-10-27T11:31:45Z2020-09-30http://repositorio.ufsm.br/handle/1/22627The stability of the SEP is a major concern for System Operators worldwide. Several actions and controls are taken when a major disturbance occurs, with the aim of finding a new balance point, minimizing the disconnection of loads and avoiding generalized blackouts. One of the most important controls is the Under Frequency Load Shedding (UFLS), in Brazil called the Regional Load Relief Scheme (ERAC). This function has already avoided several blackouts with selective load cuts by underfrequency, bringing the system to the load-generation balance. ERAC’s performance is important for the stability of the National Interconnected System (SIN), however, the improper performance of this function generates problems for concessionaires, such as customer dissatisfaction and fines imposed by the National Electric Energy Agency - ANEEL. Following this reasoning, this paper analyzes the reliability of the ERAC system in SIN disturbances and some undue actions, influenced by the deceleration of induction motors. Then, the characteristic of the voltage wave that arises due to the influence of the motors is analyzed, with the aid of the DIgSILENT software, as well as which are the ideal settings for commercial underfrequency relays in the South region. This analysis was aided by the ANATEM software, by oscillographic records of actual actions by the SIN and undue actions by the RGE concessionaire underfrequency relays. Finally, a new ERAC schemes is proposed, obtained from two settings for the blocking voltage. As result, there is the blocking of the ANSI 81U function during engine the deceleration and the guarantee of the correct performance of the ERAC when it is requested.A estabilidade do SEP é um assunto que preocupa muito os Operadores do Sistema em todo o mundo. Várias ações são executadas frente a uma grande perturbação com o objetivo de encontrar um novo ponto de equilíbrio, minimizando o desligamento de cargas e evitando blecautes generalizados. Uma importante ação realizada é o Under Frequency Load Shedding – UFLS, no Brasil denominado Esquema Regional de Alívio de Carga (ERAC). Esta função já evitou vários blecautes com cortes de carga seletivas por subfrequência, levando o sistema ao equilíbrio carga-geração. Se por um lado a atuação do ERAC é importante para a estabilidade do SIN, por outro, a atuação indevida desta função gera problemas às concessionárias, como a insatisfação dos clientes e as multas aplicadas pela Agência Nacional de Energia Elétrica – ANEEL. Seguindo este raciocínio, este trabalho analisa a confiabilidade do sistema ERAC em perturbações do SIN e algumas atuações indevidas influenciadas pela desaceleração de motores de indução. Em seguida, é analisada a característica da onda da tensão que surge por influência da contribuição dos motores, com o auxílio do software DIgSILENT, bem como são discutidos quais devem ser os ajustes ideais para os relés de subfrequência comerciais da região Sul. Esta análise foi auxiliada pelo software ANATEM, por registros oscilográficos de atuações reais do SIN e de atuações indevidas dos relés de subfrequência de alimentadores da concessionária RGE. Por fim, é proposto um novo esquema para o ERAC, obtido a partir de dois ajustes para a tensão de bloqueio. Como resultado, tem-se o bloqueio da função ANSI 81U durante a desaceleração de motores e a garantia da atuação correta do ERAC quando este for requisitado.porUniversidade Federal de Santa MariaCentro de TecnologiaPrograma de Pós-Graduação em Engenharia ElétricaUFSMBrasilEngenharia ElétricaAttribution-NonCommercial-NoDerivatives 4.0 Internationalhttp://creativecommons.org/licenses/by-nc-nd/4.0/info:eu-repo/semantics/openAccessEracSubfrequênciaRelés de frequênciaSINRegional load relief schemeUderfrequencyFrequency relaysCNPQ::ENGENHARIAS::ENGENHARIA ELETRICAAnálise de atuação indevida do ERAC em desenergização de subestação, influenciada pela desaceleração de motores e proposta de lógica utilizando a função ANSI 81U com dois estágios de tensão de bloqueio e temporizaçãoAnalysis of undue ERAC perfomance in substation de-energization , influenced by motor deceleration and logic proposal using ANSI 81U function with two stages of blocking voltage and timinginfo:eu-repo/semantics/publishedVersioninfo:eu-repo/semantics/masterThesisCardoso Junior, Ghendyhttp://lattes.cnpq.br/6284386218725402Marchesan, GustavoSantos, Eduardo Machado dosBorges, Adriano300400000007600600600eed4f55e-1a74-47ce-afc0-4daa8655d8a3ab973855-0ecc-449d-b7ad-e29f2b3622978d6a259c-1570-4739-89b0-f0525ab1200e67875026-fc93-47b0-baa7-ade5ac224343reponame:Repositório Institucional Manancial UFSMinstname:Universidade Federal de Santa Maria (UFSM)instacron:UFSMORIGINALDIS_PPGEE_2020_BORGES_ADRIANO.pdfDIS_PPGEE_2020_BORGES_ADRIANO.pdfDissertação de Mestradoapplication/pdf5200510http://repositorio.ufsm.br/bitstream/1/22627/1/DIS_PPGEE_2020_BORGES_ADRIANO.pdfe9e069fdd71934e4829975192a3fb664MD51CC-LICENSElicense_rdflicense_rdfapplication/rdf+xml; charset=utf-8805http://repositorio.ufsm.br/bitstream/1/22627/2/license_rdf4460e5956bc1d1639be9ae6146a50347MD52LICENSElicense.txtlicense.txttext/plain; charset=utf-81956http://repositorio.ufsm.br/bitstream/1/22627/3/license.txt2f0571ecee68693bd5cd3f17c1e075dfMD53TEXTDIS_PPGEE_2020_BORGES_ADRIANO.pdf.txtDIS_PPGEE_2020_BORGES_ADRIANO.pdf.txtExtracted texttext/plain189415http://repositorio.ufsm.br/bitstream/1/22627/4/DIS_PPGEE_2020_BORGES_ADRIANO.pdf.txt8b99021b3d959c28cf88d99526e2bc01MD54THUMBNAILDIS_PPGEE_2020_BORGES_ADRIANO.pdf.jpgDIS_PPGEE_2020_BORGES_ADRIANO.pdf.jpgIM Thumbnailimage/jpeg4906http://repositorio.ufsm.br/bitstream/1/22627/5/DIS_PPGEE_2020_BORGES_ADRIANO.pdf.jpgac8a58bde8224a087b3db9fc5da98d2dMD551/226272022-04-11 08:56:58.079oai:repositorio.ufsm.br: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ório Institucionalhttp://repositorio.ufsm.br/PUBhttp://repositorio.ufsm.br/oai/requestouvidoria@ufsm.bropendoar:39132022-04-11T11:56:58Repositório Institucional Manancial UFSM - Universidade Federal de Santa Maria (UFSM)false
dc.title.por.fl_str_mv Análise de atuação indevida do ERAC em desenergização de subestação, influenciada pela desaceleração de motores e proposta de lógica utilizando a função ANSI 81U com dois estágios de tensão de bloqueio e temporização
dc.title.alternative.eng.fl_str_mv Analysis of undue ERAC perfomance in substation de-energization , influenced by motor deceleration and logic proposal using ANSI 81U function with two stages of blocking voltage and timing
title Análise de atuação indevida do ERAC em desenergização de subestação, influenciada pela desaceleração de motores e proposta de lógica utilizando a função ANSI 81U com dois estágios de tensão de bloqueio e temporização
spellingShingle Análise de atuação indevida do ERAC em desenergização de subestação, influenciada pela desaceleração de motores e proposta de lógica utilizando a função ANSI 81U com dois estágios de tensão de bloqueio e temporização
Borges, Adriano
Erac
Subfrequência
Relés de frequência
SIN
Regional load relief scheme
Uderfrequency
Frequency relays
CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA
title_short Análise de atuação indevida do ERAC em desenergização de subestação, influenciada pela desaceleração de motores e proposta de lógica utilizando a função ANSI 81U com dois estágios de tensão de bloqueio e temporização
title_full Análise de atuação indevida do ERAC em desenergização de subestação, influenciada pela desaceleração de motores e proposta de lógica utilizando a função ANSI 81U com dois estágios de tensão de bloqueio e temporização
title_fullStr Análise de atuação indevida do ERAC em desenergização de subestação, influenciada pela desaceleração de motores e proposta de lógica utilizando a função ANSI 81U com dois estágios de tensão de bloqueio e temporização
title_full_unstemmed Análise de atuação indevida do ERAC em desenergização de subestação, influenciada pela desaceleração de motores e proposta de lógica utilizando a função ANSI 81U com dois estágios de tensão de bloqueio e temporização
title_sort Análise de atuação indevida do ERAC em desenergização de subestação, influenciada pela desaceleração de motores e proposta de lógica utilizando a função ANSI 81U com dois estágios de tensão de bloqueio e temporização
dc.creator.Lattes.por.fl_str_mv
author Borges, Adriano
author_facet Borges, Adriano
author_role author
dc.contributor.advisor1.fl_str_mv Cardoso Junior, Ghendy
dc.contributor.advisor1Lattes.fl_str_mv http://lattes.cnpq.br/6284386218725402
dc.contributor.referee1.fl_str_mv Marchesan, Gustavo
dc.contributor.referee2.fl_str_mv Santos, Eduardo Machado dos
dc.contributor.author.fl_str_mv Borges, Adriano
contributor_str_mv Cardoso Junior, Ghendy
Marchesan, Gustavo
Santos, Eduardo Machado dos
dc.subject.por.fl_str_mv Erac
Subfrequência
Relés de frequência
SIN
topic Erac
Subfrequência
Relés de frequência
SIN
Regional load relief scheme
Uderfrequency
Frequency relays
CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA
dc.subject.eng.fl_str_mv Regional load relief scheme
Uderfrequency
Frequency relays
dc.subject.cnpq.fl_str_mv CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA
description The stability of the SEP is a major concern for System Operators worldwide. Several actions and controls are taken when a major disturbance occurs, with the aim of finding a new balance point, minimizing the disconnection of loads and avoiding generalized blackouts. One of the most important controls is the Under Frequency Load Shedding (UFLS), in Brazil called the Regional Load Relief Scheme (ERAC). This function has already avoided several blackouts with selective load cuts by underfrequency, bringing the system to the load-generation balance. ERAC’s performance is important for the stability of the National Interconnected System (SIN), however, the improper performance of this function generates problems for concessionaires, such as customer dissatisfaction and fines imposed by the National Electric Energy Agency - ANEEL. Following this reasoning, this paper analyzes the reliability of the ERAC system in SIN disturbances and some undue actions, influenced by the deceleration of induction motors. Then, the characteristic of the voltage wave that arises due to the influence of the motors is analyzed, with the aid of the DIgSILENT software, as well as which are the ideal settings for commercial underfrequency relays in the South region. This analysis was aided by the ANATEM software, by oscillographic records of actual actions by the SIN and undue actions by the RGE concessionaire underfrequency relays. Finally, a new ERAC schemes is proposed, obtained from two settings for the blocking voltage. As result, there is the blocking of the ANSI 81U function during engine the deceleration and the guarantee of the correct performance of the ERAC when it is requested.
publishDate 2020
dc.date.issued.fl_str_mv 2020-09-30
dc.date.accessioned.fl_str_mv 2021-10-27T11:31:45Z
dc.date.available.fl_str_mv 2021-10-27T11:31:45Z
dc.type.status.fl_str_mv info:eu-repo/semantics/publishedVersion
dc.type.driver.fl_str_mv info:eu-repo/semantics/masterThesis
format masterThesis
status_str publishedVersion
dc.identifier.uri.fl_str_mv http://repositorio.ufsm.br/handle/1/22627
url http://repositorio.ufsm.br/handle/1/22627
dc.language.iso.fl_str_mv por
language por
dc.relation.cnpq.fl_str_mv 300400000007
dc.relation.confidence.fl_str_mv 600
600
600
dc.relation.authority.fl_str_mv eed4f55e-1a74-47ce-afc0-4daa8655d8a3
ab973855-0ecc-449d-b7ad-e29f2b362297
8d6a259c-1570-4739-89b0-f0525ab1200e
67875026-fc93-47b0-baa7-ade5ac224343
dc.rights.driver.fl_str_mv Attribution-NonCommercial-NoDerivatives 4.0 International
http://creativecommons.org/licenses/by-nc-nd/4.0/
info:eu-repo/semantics/openAccess
rights_invalid_str_mv Attribution-NonCommercial-NoDerivatives 4.0 International
http://creativecommons.org/licenses/by-nc-nd/4.0/
eu_rights_str_mv openAccess
dc.publisher.none.fl_str_mv Universidade Federal de Santa Maria
Centro de Tecnologia
dc.publisher.program.fl_str_mv Programa de Pós-Graduação em Engenharia Elétrica
dc.publisher.initials.fl_str_mv UFSM
dc.publisher.country.fl_str_mv Brasil
dc.publisher.department.fl_str_mv Engenharia Elétrica
publisher.none.fl_str_mv Universidade Federal de Santa Maria
Centro de Tecnologia
dc.source.none.fl_str_mv reponame:Repositório Institucional Manancial UFSM
instname:Universidade Federal de Santa Maria (UFSM)
instacron:UFSM
instname_str Universidade Federal de Santa Maria (UFSM)
instacron_str UFSM
institution UFSM
reponame_str Repositório Institucional Manancial UFSM
collection Repositório Institucional Manancial UFSM
bitstream.url.fl_str_mv http://repositorio.ufsm.br/bitstream/1/22627/1/DIS_PPGEE_2020_BORGES_ADRIANO.pdf
http://repositorio.ufsm.br/bitstream/1/22627/2/license_rdf
http://repositorio.ufsm.br/bitstream/1/22627/3/license.txt
http://repositorio.ufsm.br/bitstream/1/22627/4/DIS_PPGEE_2020_BORGES_ADRIANO.pdf.txt
http://repositorio.ufsm.br/bitstream/1/22627/5/DIS_PPGEE_2020_BORGES_ADRIANO.pdf.jpg
bitstream.checksum.fl_str_mv e9e069fdd71934e4829975192a3fb664
4460e5956bc1d1639be9ae6146a50347
2f0571ecee68693bd5cd3f17c1e075df
8b99021b3d959c28cf88d99526e2bc01
ac8a58bde8224a087b3db9fc5da98d2d
bitstream.checksumAlgorithm.fl_str_mv MD5
MD5
MD5
MD5
MD5
repository.name.fl_str_mv Repositório Institucional Manancial UFSM - Universidade Federal de Santa Maria (UFSM)
repository.mail.fl_str_mv ouvidoria@ufsm.br
_version_ 1808854720175931392