Análise experimental da eficiência energética de um sistema de refrigeração automatizado utilizando R22 e propileno como fluido refrigerante

Detalhes bibliográficos
Autor(a) principal: Antunes, Arthur Heleno Pontes
Data de Publicação: 2011
Tipo de documento: Dissertação
Idioma: por
Título da fonte: Repositório Institucional da UFU
Texto Completo: https://repositorio.ufu.br/handle/123456789/14879
Resumo: This work contributed to the knowledge about the necessity to replace halogenated fluids by natural refrigerants reducing the damage to the environment. Primarily, it became necessary to know the operation limits of an experimental facility that could be an air conditioning system with maximum refrigerating capacity of 15 kW, operating during summer. At the same time and collectively as the first objective, instrumentation and control strategies were adopted, allowing extending the focus of this research on another topic, energy savings of air conditioning systems. The experimental facility has been submitted at three different configurations: the first one depicted a conventional air conditioning system that, basically, consists of a reciprocating compressor working at nominal frequency, two concentric tubes heat exchanger, a thermostatic expansion valve (TEV) and R22 as refrigerant fluid; in the second case, the compressor speed was controlled by an inverter frequency drive and an electronic expansion valve replaced the TEV; and finally it was proposed a third system configuration, exactly to the second one, in which was used R1270 (propylene) as the working fluid. The results showed that the system operating at frequencies below 60 Hz and the implementation of a PID controller in the mechanism of expansion enabled the improvement in the COP of the automated systems compared to the COP of the conventional system, which used an on-off controller. Consequently, the automation of the conventional system reduced by 35% the average monthly consumption of electricity. The replacement of R22 by R1270 (refrigerant with a smaller GWP) increased even more the values of the COP and reduced the environmental damage, calculated by the total equivalent warming impact (TEWI). It showed that the automation and the replacement of a traditional fluid by a hydrocarbon decrease in 77% the damage to the environment for this specific application.
id UFU_511efd839dc60b96ff1d2bcc767c19ef
oai_identifier_str oai:repositorio.ufu.br:123456789/14879
network_acronym_str UFU
network_name_str Repositório Institucional da UFU
repository_id_str
spelling 2016-06-22T18:40:13Z2011-06-102016-06-22T18:40:13Z2011-03-18ANTUNES, Arthur Heleno Pontes. Experimental analysis of the energy efficiency of an automated refrigeration system using R22 and propylene as refrigerant. 2011. 134 f. Dissertação (Mestrado em Engenharias) - Universidade Federal de Uberlândia, Uberlândia, 2011.https://repositorio.ufu.br/handle/123456789/14879This work contributed to the knowledge about the necessity to replace halogenated fluids by natural refrigerants reducing the damage to the environment. Primarily, it became necessary to know the operation limits of an experimental facility that could be an air conditioning system with maximum refrigerating capacity of 15 kW, operating during summer. At the same time and collectively as the first objective, instrumentation and control strategies were adopted, allowing extending the focus of this research on another topic, energy savings of air conditioning systems. The experimental facility has been submitted at three different configurations: the first one depicted a conventional air conditioning system that, basically, consists of a reciprocating compressor working at nominal frequency, two concentric tubes heat exchanger, a thermostatic expansion valve (TEV) and R22 as refrigerant fluid; in the second case, the compressor speed was controlled by an inverter frequency drive and an electronic expansion valve replaced the TEV; and finally it was proposed a third system configuration, exactly to the second one, in which was used R1270 (propylene) as the working fluid. The results showed that the system operating at frequencies below 60 Hz and the implementation of a PID controller in the mechanism of expansion enabled the improvement in the COP of the automated systems compared to the COP of the conventional system, which used an on-off controller. Consequently, the automation of the conventional system reduced by 35% the average monthly consumption of electricity. The replacement of R22 by R1270 (refrigerant with a smaller GWP) increased even more the values of the COP and reduced the environmental damage, calculated by the total equivalent warming impact (TEWI). It showed that the automation and the replacement of a traditional fluid by a hydrocarbon decrease in 77% the damage to the environment for this specific application.Este trabalho contribuiu com o conhecimento acerca da necessidade de substituir os fluidos halogenados por refrigerantes naturais e assim, reduzir os danos causados ao meioambiente. Primeiramente, tornou-se necessário conhecer os limites de operação de uma bancada experimental, a qual representou um sistema de condicionamento de ar com capacidade frigorífica máxima de 15 kW, operando em condições normais durante o verão. Paralela e conjuntamente ao objetivo principal, estratégias de instrumentação e controle foram adotadas, o que possibilitou estender o foco desta pesquisa sobre outro tema, economia de energia elétrica em sistemas de refrigeração. A bancada experimental foi submetida a três configurações distintas para a realização dos testes. A primeira delas retratou um sistema de refrigeração convencional, composto basicamente por um compressor alternativo operando a freqüência nominal, dois trocadores de calor de tubos concêntricos, uma válvula de expansão termostática (VET) e o fluido R22 como refrigerante. Para o segundo caso, a velocidade do compressor foi comandada por um variador de freqüência e uma válvula de expansão eletrônica substituiu a VET, os outros parâmetros foram mantidos. A terceira configuração do sistema foi exatamente igual à segunda, porém utilizou-se R1270 (propileno) com fluido de trabalho. Os resultados mostraram que a operação do sistema em freqüências inferiores a 60 Hz e a aplicação de um controlador PID no mecanismo de expansão permitiu o melhoramento no COP dos sistemas automatizados em comparação ao COP do sistema convencional, que utilizou um controlador liga-desliga. Consequentemente, a automatização do sistema convencional proporcionou uma redução de 35% no consumo médio mensal de energia elétrica. A substituição do R22 pelo R1270 (refrigerante com GWP inferior) elevou ainda mais os valores do COP e reduziu os danos ambientais, calculados com base no impacto total de aquecimento equivalente (TEWI). Comprovou-se que para esta aplicação específica, a automatização e a substituição do fluido tradicional por um hidrocarboneto reduzem em 77% os danos ao meio-ambiente.Conselho Nacional de Desenvolvimento Científico e TecnológicoMestre em Engenharia Mecânicaapplication/pdfporUniversidade Federal de UberlândiaPrograma de Pós-graduação em Engenharia MecânicaUFUBREngenhariasSistemas de refrigeraçãoHidrocarbonetoControleR22R1270COPFluidos refrigerantesRefrigeraçãoRefrigeration systemsHydrocarbonControlCNPQ::ENGENHARIAS::ENGENHARIA MECANICAAnálise experimental da eficiência energética de um sistema de refrigeração automatizado utilizando R22 e propileno como fluido refrigeranteExperimental analysis of the energy efficiency of an automated refrigeration system using R22 and propylene as refrigerantinfo:eu-repo/semantics/publishedVersioninfo:eu-repo/semantics/masterThesisBandarra Filho, Enio Pedonehttp://buscatextual.cnpq.br/buscatextual/visualizacv.do?id=K4702556U9Carvalho, Solidônio Rodrigues dehttp://buscatextual.cnpq.br/buscatextual/visualizacv.do?id=K4762468A6Schneider, Paulo Smithhttp://buscatextual.cnpq.br/buscatextual/visualizacv.do?id=K4782263A6http://buscatextual.cnpq.br/buscatextual/visualizacv.do?id=K4239640H4Antunes, Arthur Heleno Pontesinfo:eu-repo/semantics/openAccessreponame:Repositório Institucional da UFUinstname:Universidade Federal de Uberlândia (UFU)instacron:UFUTHUMBNAILDiss Arthur.pdf.jpgDiss Arthur.pdf.jpgGenerated Thumbnailimage/jpeg1355https://repositorio.ufu.br/bitstream/123456789/14879/3/Diss%20Arthur.pdf.jpg6162ca67d467df1897f46e62d1b53050MD53ORIGINALDiss Arthur.pdfapplication/pdf1461218https://repositorio.ufu.br/bitstream/123456789/14879/1/Diss%20Arthur.pdfc32777aa9a761a9ecc542c0d15d1b48bMD51TEXTDiss Arthur.pdf.txtDiss Arthur.pdf.txtExtracted texttext/plain223865https://repositorio.ufu.br/bitstream/123456789/14879/2/Diss%20Arthur.pdf.txte5003b5bd76ce18472de1fda20e2c028MD52123456789/148792016-06-23 04:07:27.054oai:repositorio.ufu.br:123456789/14879Repositório InstitucionalONGhttp://repositorio.ufu.br/oai/requestdiinf@dirbi.ufu.bropendoar:2016-06-23T07:07:27Repositório Institucional da UFU - Universidade Federal de Uberlândia (UFU)false
dc.title.por.fl_str_mv Análise experimental da eficiência energética de um sistema de refrigeração automatizado utilizando R22 e propileno como fluido refrigerante
dc.title.alternative.eng.fl_str_mv Experimental analysis of the energy efficiency of an automated refrigeration system using R22 and propylene as refrigerant
title Análise experimental da eficiência energética de um sistema de refrigeração automatizado utilizando R22 e propileno como fluido refrigerante
spellingShingle Análise experimental da eficiência energética de um sistema de refrigeração automatizado utilizando R22 e propileno como fluido refrigerante
Antunes, Arthur Heleno Pontes
Sistemas de refrigeração
Hidrocarboneto
Controle
R22
R1270
COP
Fluidos refrigerantes
Refrigeração
Refrigeration systems
Hydrocarbon
Control
CNPQ::ENGENHARIAS::ENGENHARIA MECANICA
title_short Análise experimental da eficiência energética de um sistema de refrigeração automatizado utilizando R22 e propileno como fluido refrigerante
title_full Análise experimental da eficiência energética de um sistema de refrigeração automatizado utilizando R22 e propileno como fluido refrigerante
title_fullStr Análise experimental da eficiência energética de um sistema de refrigeração automatizado utilizando R22 e propileno como fluido refrigerante
title_full_unstemmed Análise experimental da eficiência energética de um sistema de refrigeração automatizado utilizando R22 e propileno como fluido refrigerante
title_sort Análise experimental da eficiência energética de um sistema de refrigeração automatizado utilizando R22 e propileno como fluido refrigerante
author Antunes, Arthur Heleno Pontes
author_facet Antunes, Arthur Heleno Pontes
author_role author
dc.contributor.advisor1.fl_str_mv Bandarra Filho, Enio Pedone
dc.contributor.advisor1Lattes.fl_str_mv http://buscatextual.cnpq.br/buscatextual/visualizacv.do?id=K4702556U9
dc.contributor.referee1.fl_str_mv Carvalho, Solidônio Rodrigues de
dc.contributor.referee1Lattes.fl_str_mv http://buscatextual.cnpq.br/buscatextual/visualizacv.do?id=K4762468A6
dc.contributor.referee2.fl_str_mv Schneider, Paulo Smith
dc.contributor.referee2Lattes.fl_str_mv http://buscatextual.cnpq.br/buscatextual/visualizacv.do?id=K4782263A6
dc.contributor.authorLattes.fl_str_mv http://buscatextual.cnpq.br/buscatextual/visualizacv.do?id=K4239640H4
dc.contributor.author.fl_str_mv Antunes, Arthur Heleno Pontes
contributor_str_mv Bandarra Filho, Enio Pedone
Carvalho, Solidônio Rodrigues de
Schneider, Paulo Smith
dc.subject.por.fl_str_mv Sistemas de refrigeração
Hidrocarboneto
Controle
R22
R1270
COP
Fluidos refrigerantes
Refrigeração
topic Sistemas de refrigeração
Hidrocarboneto
Controle
R22
R1270
COP
Fluidos refrigerantes
Refrigeração
Refrigeration systems
Hydrocarbon
Control
CNPQ::ENGENHARIAS::ENGENHARIA MECANICA
dc.subject.eng.fl_str_mv Refrigeration systems
Hydrocarbon
Control
dc.subject.cnpq.fl_str_mv CNPQ::ENGENHARIAS::ENGENHARIA MECANICA
description This work contributed to the knowledge about the necessity to replace halogenated fluids by natural refrigerants reducing the damage to the environment. Primarily, it became necessary to know the operation limits of an experimental facility that could be an air conditioning system with maximum refrigerating capacity of 15 kW, operating during summer. At the same time and collectively as the first objective, instrumentation and control strategies were adopted, allowing extending the focus of this research on another topic, energy savings of air conditioning systems. The experimental facility has been submitted at three different configurations: the first one depicted a conventional air conditioning system that, basically, consists of a reciprocating compressor working at nominal frequency, two concentric tubes heat exchanger, a thermostatic expansion valve (TEV) and R22 as refrigerant fluid; in the second case, the compressor speed was controlled by an inverter frequency drive and an electronic expansion valve replaced the TEV; and finally it was proposed a third system configuration, exactly to the second one, in which was used R1270 (propylene) as the working fluid. The results showed that the system operating at frequencies below 60 Hz and the implementation of a PID controller in the mechanism of expansion enabled the improvement in the COP of the automated systems compared to the COP of the conventional system, which used an on-off controller. Consequently, the automation of the conventional system reduced by 35% the average monthly consumption of electricity. The replacement of R22 by R1270 (refrigerant with a smaller GWP) increased even more the values of the COP and reduced the environmental damage, calculated by the total equivalent warming impact (TEWI). It showed that the automation and the replacement of a traditional fluid by a hydrocarbon decrease in 77% the damage to the environment for this specific application.
publishDate 2011
dc.date.available.fl_str_mv 2011-06-10
2016-06-22T18:40:13Z
dc.date.issued.fl_str_mv 2011-03-18
dc.date.accessioned.fl_str_mv 2016-06-22T18:40:13Z
dc.type.status.fl_str_mv info:eu-repo/semantics/publishedVersion
dc.type.driver.fl_str_mv info:eu-repo/semantics/masterThesis
format masterThesis
status_str publishedVersion
dc.identifier.citation.fl_str_mv ANTUNES, Arthur Heleno Pontes. Experimental analysis of the energy efficiency of an automated refrigeration system using R22 and propylene as refrigerant. 2011. 134 f. Dissertação (Mestrado em Engenharias) - Universidade Federal de Uberlândia, Uberlândia, 2011.
dc.identifier.uri.fl_str_mv https://repositorio.ufu.br/handle/123456789/14879
identifier_str_mv ANTUNES, Arthur Heleno Pontes. Experimental analysis of the energy efficiency of an automated refrigeration system using R22 and propylene as refrigerant. 2011. 134 f. Dissertação (Mestrado em Engenharias) - Universidade Federal de Uberlândia, Uberlândia, 2011.
url https://repositorio.ufu.br/handle/123456789/14879
dc.language.iso.fl_str_mv por
language por
dc.rights.driver.fl_str_mv info:eu-repo/semantics/openAccess
eu_rights_str_mv openAccess
dc.format.none.fl_str_mv application/pdf
dc.publisher.none.fl_str_mv Universidade Federal de Uberlândia
dc.publisher.program.fl_str_mv Programa de Pós-graduação em Engenharia Mecânica
dc.publisher.initials.fl_str_mv UFU
dc.publisher.country.fl_str_mv BR
dc.publisher.department.fl_str_mv Engenharias
publisher.none.fl_str_mv Universidade Federal de Uberlândia
dc.source.none.fl_str_mv reponame:Repositório Institucional da UFU
instname:Universidade Federal de Uberlândia (UFU)
instacron:UFU
instname_str Universidade Federal de Uberlândia (UFU)
instacron_str UFU
institution UFU
reponame_str Repositório Institucional da UFU
collection Repositório Institucional da UFU
bitstream.url.fl_str_mv https://repositorio.ufu.br/bitstream/123456789/14879/3/Diss%20Arthur.pdf.jpg
https://repositorio.ufu.br/bitstream/123456789/14879/1/Diss%20Arthur.pdf
https://repositorio.ufu.br/bitstream/123456789/14879/2/Diss%20Arthur.pdf.txt
bitstream.checksum.fl_str_mv 6162ca67d467df1897f46e62d1b53050
c32777aa9a761a9ecc542c0d15d1b48b
e5003b5bd76ce18472de1fda20e2c028
bitstream.checksumAlgorithm.fl_str_mv MD5
MD5
MD5
repository.name.fl_str_mv Repositório Institucional da UFU - Universidade Federal de Uberlândia (UFU)
repository.mail.fl_str_mv diinf@dirbi.ufu.br
_version_ 1802110425670615040