Análise da disponibilidade de iluminação natural e artificial em salas de aula de instituição pública de ensino superior

Detalhes bibliográficos
Autor(a) principal: Mansilha, Raquel Brandão
Data de Publicação: 2013
Tipo de documento: Dissertação
Idioma: por
Título da fonte: Biblioteca Digital de Teses e Dissertações do UFSM
Texto Completo: http://repositorio.ufsm.br/handle/1/7832
Resumo: The classrooms are the more permanent environments at schools; therefore their thermal, visual and acoustic characteristics must be carefully considered. Visual comfort can be achieved only with daylighting; artificial lighting is necessary when the daylighting is insufficient. The artificial lighting is responsible for high energy consumption in buildings. According to Klüsener (2009), who analysed a building of UFSM in accordance with Brazilian energy efficiency standards (RTQ-C), the artificial lighting systems reached the level E (on a A-E scale). In general, simple actions could be improving the energy efficiency of the building lighting system. Considering that the university buildings have a similar performance, the adaptation of lighting systems is important for low-energy consumption. This study aims to define classrooms guidelines for visual comfort in accordance with illuminance levels available and their distribution on the work surface where tasks are performed, as well as the energy efficiency of the classrooms lighting systems. The classrooms were selected to represent the existing universe buildings. The classrooms were characterized with regard to dimensions, surface light reflections, opening systems, solar orientation, sun shading systems, external obstructions and artificial electrical lighting systems. The illuminance levels were measured in two classrooms simultaneously with Instrutherm luximeters, model LDR 225. The measurements were in accordance with the Brazilian standards (NBR 15215) and were carried out at six points on an orthogonal grid. A comparative analysis was made for the classrooms that were simultaneously measured. Additionally the partial RTQ-C lighting criteria were applied on the classrooms lighting systems and the theoretical external illuminance levels were calculated in order to generate the daylight factor (DF). The results pointed that the internal daylight distribution is affected by external obstructions that reduce the portion of visible sky and these are not considered in the windows design. For simultaneous daylighting and artificial lighting, the illuminance levels are excessive and poorly distributed; consequently they cause high energy consumption. The existence of unnecessary sun shading systems, for southern solar orientations and for windows with complete sky obstructions, contributes for the insufficient classrooms illuminance levels. The RTQ-C criteria analysis point levels E and C for the classrooms. In general, the DF do not correspond to expected values indicated by international recommendations.
id UFSM_b102cc4a97439693ed8ffe46610c761a
oai_identifier_str oai:repositorio.ufsm.br:1/7832
network_acronym_str UFSM
network_name_str Biblioteca Digital de Teses e Dissertações do UFSM
repository_id_str
spelling 2014-09-152014-09-152013-06-20MANSILHA, Raquel Brandão. Analysis of availability of natural and artificial lighting in classrooms in public institution of higher education. 2013. 188 f. Dissertação (Mestrado em Engenharia Civil) - Universidade Federal de Santa Maria, Santa Maria, 2013.http://repositorio.ufsm.br/handle/1/7832The classrooms are the more permanent environments at schools; therefore their thermal, visual and acoustic characteristics must be carefully considered. Visual comfort can be achieved only with daylighting; artificial lighting is necessary when the daylighting is insufficient. The artificial lighting is responsible for high energy consumption in buildings. According to Klüsener (2009), who analysed a building of UFSM in accordance with Brazilian energy efficiency standards (RTQ-C), the artificial lighting systems reached the level E (on a A-E scale). In general, simple actions could be improving the energy efficiency of the building lighting system. Considering that the university buildings have a similar performance, the adaptation of lighting systems is important for low-energy consumption. This study aims to define classrooms guidelines for visual comfort in accordance with illuminance levels available and their distribution on the work surface where tasks are performed, as well as the energy efficiency of the classrooms lighting systems. The classrooms were selected to represent the existing universe buildings. The classrooms were characterized with regard to dimensions, surface light reflections, opening systems, solar orientation, sun shading systems, external obstructions and artificial electrical lighting systems. The illuminance levels were measured in two classrooms simultaneously with Instrutherm luximeters, model LDR 225. The measurements were in accordance with the Brazilian standards (NBR 15215) and were carried out at six points on an orthogonal grid. A comparative analysis was made for the classrooms that were simultaneously measured. Additionally the partial RTQ-C lighting criteria were applied on the classrooms lighting systems and the theoretical external illuminance levels were calculated in order to generate the daylight factor (DF). The results pointed that the internal daylight distribution is affected by external obstructions that reduce the portion of visible sky and these are not considered in the windows design. For simultaneous daylighting and artificial lighting, the illuminance levels are excessive and poorly distributed; consequently they cause high energy consumption. The existence of unnecessary sun shading systems, for southern solar orientations and for windows with complete sky obstructions, contributes for the insufficient classrooms illuminance levels. The RTQ-C criteria analysis point levels E and C for the classrooms. In general, the DF do not correspond to expected values indicated by international recommendations.As salas de aula, por serem ambientes de maior permanência dos alunos, devem possuir condições de conforto térmico, visual e acústico adequadas. O conforto visual pode ser obtido com a iluminação natural ou com auxilio da artificial quando a natural não é suficiente. Quando se utiliza a iluminação artificial, existe a preocupação com o consumo energético da edificação. Segundo estudos realizados por Klüsener (2009), que aplicou o Regulamento Técnico da Qualidade para Etiquetagem do Nível de Eficiência Energética de Edifícios (RTQ-C) em uma edificação do campus da UFSM em Camobi, o sistema de iluminação é de baixa eficiência energética, tendo atingido o nível E. No entanto, segundo o mesmo estudo, existe um potencial para a melhoria da eficiência energética a partir de ações simples. Partindo-se do pressuposto que as outras edificações da universidade possuem um desempenho semelhante, percebe-se a importância de adequar os seus sistemas de iluminação a fim de reduzir o consumo de energia. Esse trabalho tem como objetivo apontar diretrizes que visem o conforto visual no que diz respeito aos níveis de iluminância disponíveis e sua distribuição no ambiente, bem como à eficiência energética de sistemas de iluminação de salas de aula. Para isso, foram selecionadas salas de aula que fossem representativas do universo existente no campus. Após, foram feitos os levantamentos de suas características físicas (dimensões, cores das superfícies, tipos de aberturas, orientação solar, tipos de proteções solares, presença de obstruções externas, tipos e distribuição de luminárias e lâmpadas) e foram realizadas medições in loco com luxímetros digitais da marca Instrutherm, modelo LDR 225 e segundo recomendações da NBR 15215 (ABNT, 2005d). Também foi feita uma análise parcial segundo os Requisitos Técnicos da Qualidade para o Nível de Eficiência Energética de Edifícios Comerciais, de Serviços e Públicos (RTQ-C) e uma análise comparativa entre os níveis de iluminância medidos e os coeficientes de contribuição de iluminação natural (CIN) estimados. Com os resultados obtidos, verificou-se que a distribuição da iluminação natural é afetada por condições do entorno que causam obstruções do céu visível, não sendo consideradas no projeto das aberturas. Nas medições com iluminação natural mais artificial, os níveis são excessivos e mal distribuídos, causando consumo desnecessário de energia. As proteções solares presentes nas orientações a norte desconsideram as condições do entorno. A avaliação parcial através da aplicação dos requisitos específicos do RTQ-C para os sistemas de iluminação resultou em nível E para as salas do CE e em nível C para as outras. Os CIN calculados em grande parte do tempo não corresponderam aos valores teóricos esperados para salas de aula, conforme literatura.Coordenação de Aperfeiçoamento de Pessoal de Nível Superiorapplication/pdfporUniversidade Federal de Santa MariaPrograma de Pós-Graduação em Engenharia CivilUFSMBREngenharia CivilConforto visualEficiência energéticaSistemas de iluminaçãoSalas de aulaVisual comfortEnergy efficiencyLighting systemsClassroomsCNPQ::ENGENHARIAS::ENGENHARIA CIVILAnálise da disponibilidade de iluminação natural e artificial em salas de aula de instituição pública de ensino superiorAnalysis of availability of natural and artificial lighting in classrooms in public institution of higher educationinfo:eu-repo/semantics/publishedVersioninfo:eu-repo/semantics/masterThesisGrigoletti, Giane de Camposhttp://lattes.cnpq.br/9725292275606192Correa, Celina Maria Brittohttp://lattes.cnpq.br/2741252699364572Santos, Joaquim Cesar Pizzutti doshttp://lattes.cnpq.br/6591314076760539http://lattes.cnpq.br/0912738432121227Mansilha, Raquel Brandão3001000000034003003003003001de16499-3baf-492b-8484-6e4d8f2f2768265e952a-be66-4cb1-96e7-ab8dd1b246d305a1e28b-ee3a-456b-86dc-316aebf2d61de75b92c9-d444-4263-85c5-15279c14165einfo:eu-repo/semantics/openAccessreponame:Biblioteca Digital de Teses e Dissertações do UFSMinstname:Universidade Federal de Santa Maria (UFSM)instacron:UFSMORIGINALMANSILHA, RAQUEL BRANDAO.pdfapplication/pdf7935776http://repositorio.ufsm.br/bitstream/1/7832/1/MANSILHA%2c%20RAQUEL%20BRANDAO.pdf6f9af73efd4a662d65ea6b8b782b3d29MD51TEXTMANSILHA, RAQUEL BRANDAO.pdf.txtMANSILHA, RAQUEL BRANDAO.pdf.txtExtracted texttext/plain287399http://repositorio.ufsm.br/bitstream/1/7832/2/MANSILHA%2c%20RAQUEL%20BRANDAO.pdf.txt111b5721adaa88ef30d8f1c0d20dc225MD52THUMBNAILMANSILHA, RAQUEL BRANDAO.pdf.jpgMANSILHA, RAQUEL BRANDAO.pdf.jpgIM Thumbnailimage/jpeg4991http://repositorio.ufsm.br/bitstream/1/7832/3/MANSILHA%2c%20RAQUEL%20BRANDAO.pdf.jpg5d0ce8d2845fdad750247bad562c2107MD531/78322023-06-12 09:30:38.908oai:repositorio.ufsm.br:1/7832Biblioteca Digital de Teses e Dissertaçõeshttps://repositorio.ufsm.br/ONGhttps://repositorio.ufsm.br/oai/requestatendimento.sib@ufsm.br||tedebc@gmail.comopendoar:2023-06-12T12:30:38Biblioteca Digital de Teses e Dissertações do UFSM - Universidade Federal de Santa Maria (UFSM)false
dc.title.por.fl_str_mv Análise da disponibilidade de iluminação natural e artificial em salas de aula de instituição pública de ensino superior
dc.title.alternative.eng.fl_str_mv Analysis of availability of natural and artificial lighting in classrooms in public institution of higher education
title Análise da disponibilidade de iluminação natural e artificial em salas de aula de instituição pública de ensino superior
spellingShingle Análise da disponibilidade de iluminação natural e artificial em salas de aula de instituição pública de ensino superior
Mansilha, Raquel Brandão
Conforto visual
Eficiência energética
Sistemas de iluminação
Salas de aula
Visual comfort
Energy efficiency
Lighting systems
Classrooms
CNPQ::ENGENHARIAS::ENGENHARIA CIVIL
title_short Análise da disponibilidade de iluminação natural e artificial em salas de aula de instituição pública de ensino superior
title_full Análise da disponibilidade de iluminação natural e artificial em salas de aula de instituição pública de ensino superior
title_fullStr Análise da disponibilidade de iluminação natural e artificial em salas de aula de instituição pública de ensino superior
title_full_unstemmed Análise da disponibilidade de iluminação natural e artificial em salas de aula de instituição pública de ensino superior
title_sort Análise da disponibilidade de iluminação natural e artificial em salas de aula de instituição pública de ensino superior
author Mansilha, Raquel Brandão
author_facet Mansilha, Raquel Brandão
author_role author
dc.contributor.advisor1.fl_str_mv Grigoletti, Giane de Campos
dc.contributor.advisor1Lattes.fl_str_mv http://lattes.cnpq.br/9725292275606192
dc.contributor.referee1.fl_str_mv Correa, Celina Maria Britto
dc.contributor.referee1Lattes.fl_str_mv http://lattes.cnpq.br/2741252699364572
dc.contributor.referee2.fl_str_mv Santos, Joaquim Cesar Pizzutti dos
dc.contributor.referee2Lattes.fl_str_mv http://lattes.cnpq.br/6591314076760539
dc.contributor.authorLattes.fl_str_mv http://lattes.cnpq.br/0912738432121227
dc.contributor.author.fl_str_mv Mansilha, Raquel Brandão
contributor_str_mv Grigoletti, Giane de Campos
Correa, Celina Maria Britto
Santos, Joaquim Cesar Pizzutti dos
dc.subject.por.fl_str_mv Conforto visual
Eficiência energética
Sistemas de iluminação
Salas de aula
topic Conforto visual
Eficiência energética
Sistemas de iluminação
Salas de aula
Visual comfort
Energy efficiency
Lighting systems
Classrooms
CNPQ::ENGENHARIAS::ENGENHARIA CIVIL
dc.subject.eng.fl_str_mv Visual comfort
Energy efficiency
Lighting systems
Classrooms
dc.subject.cnpq.fl_str_mv CNPQ::ENGENHARIAS::ENGENHARIA CIVIL
description The classrooms are the more permanent environments at schools; therefore their thermal, visual and acoustic characteristics must be carefully considered. Visual comfort can be achieved only with daylighting; artificial lighting is necessary when the daylighting is insufficient. The artificial lighting is responsible for high energy consumption in buildings. According to Klüsener (2009), who analysed a building of UFSM in accordance with Brazilian energy efficiency standards (RTQ-C), the artificial lighting systems reached the level E (on a A-E scale). In general, simple actions could be improving the energy efficiency of the building lighting system. Considering that the university buildings have a similar performance, the adaptation of lighting systems is important for low-energy consumption. This study aims to define classrooms guidelines for visual comfort in accordance with illuminance levels available and their distribution on the work surface where tasks are performed, as well as the energy efficiency of the classrooms lighting systems. The classrooms were selected to represent the existing universe buildings. The classrooms were characterized with regard to dimensions, surface light reflections, opening systems, solar orientation, sun shading systems, external obstructions and artificial electrical lighting systems. The illuminance levels were measured in two classrooms simultaneously with Instrutherm luximeters, model LDR 225. The measurements were in accordance with the Brazilian standards (NBR 15215) and were carried out at six points on an orthogonal grid. A comparative analysis was made for the classrooms that were simultaneously measured. Additionally the partial RTQ-C lighting criteria were applied on the classrooms lighting systems and the theoretical external illuminance levels were calculated in order to generate the daylight factor (DF). The results pointed that the internal daylight distribution is affected by external obstructions that reduce the portion of visible sky and these are not considered in the windows design. For simultaneous daylighting and artificial lighting, the illuminance levels are excessive and poorly distributed; consequently they cause high energy consumption. The existence of unnecessary sun shading systems, for southern solar orientations and for windows with complete sky obstructions, contributes for the insufficient classrooms illuminance levels. The RTQ-C criteria analysis point levels E and C for the classrooms. In general, the DF do not correspond to expected values indicated by international recommendations.
publishDate 2013
dc.date.issued.fl_str_mv 2013-06-20
dc.date.accessioned.fl_str_mv 2014-09-15
dc.date.available.fl_str_mv 2014-09-15
dc.type.status.fl_str_mv info:eu-repo/semantics/publishedVersion
dc.type.driver.fl_str_mv info:eu-repo/semantics/masterThesis
format masterThesis
status_str publishedVersion
dc.identifier.citation.fl_str_mv MANSILHA, Raquel Brandão. Analysis of availability of natural and artificial lighting in classrooms in public institution of higher education. 2013. 188 f. Dissertação (Mestrado em Engenharia Civil) - Universidade Federal de Santa Maria, Santa Maria, 2013.
dc.identifier.uri.fl_str_mv http://repositorio.ufsm.br/handle/1/7832
identifier_str_mv MANSILHA, Raquel Brandão. Analysis of availability of natural and artificial lighting in classrooms in public institution of higher education. 2013. 188 f. Dissertação (Mestrado em Engenharia Civil) - Universidade Federal de Santa Maria, Santa Maria, 2013.
url http://repositorio.ufsm.br/handle/1/7832
dc.language.iso.fl_str_mv por
language por
dc.relation.cnpq.fl_str_mv 300100000003
dc.relation.confidence.fl_str_mv 400
300
300
300
300
dc.relation.authority.fl_str_mv 1de16499-3baf-492b-8484-6e4d8f2f2768
265e952a-be66-4cb1-96e7-ab8dd1b246d3
05a1e28b-ee3a-456b-86dc-316aebf2d61d
e75b92c9-d444-4263-85c5-15279c14165e
dc.rights.driver.fl_str_mv info:eu-repo/semantics/openAccess
eu_rights_str_mv openAccess
dc.format.none.fl_str_mv application/pdf
dc.publisher.none.fl_str_mv Universidade Federal de Santa Maria
dc.publisher.program.fl_str_mv Programa de Pós-Graduação em Engenharia Civil
dc.publisher.initials.fl_str_mv UFSM
dc.publisher.country.fl_str_mv BR
dc.publisher.department.fl_str_mv Engenharia Civil
publisher.none.fl_str_mv Universidade Federal de Santa Maria
dc.source.none.fl_str_mv reponame:Biblioteca Digital de Teses e Dissertações do UFSM
instname:Universidade Federal de Santa Maria (UFSM)
instacron:UFSM
instname_str Universidade Federal de Santa Maria (UFSM)
instacron_str UFSM
institution UFSM
reponame_str Biblioteca Digital de Teses e Dissertações do UFSM
collection Biblioteca Digital de Teses e Dissertações do UFSM
bitstream.url.fl_str_mv http://repositorio.ufsm.br/bitstream/1/7832/1/MANSILHA%2c%20RAQUEL%20BRANDAO.pdf
http://repositorio.ufsm.br/bitstream/1/7832/2/MANSILHA%2c%20RAQUEL%20BRANDAO.pdf.txt
http://repositorio.ufsm.br/bitstream/1/7832/3/MANSILHA%2c%20RAQUEL%20BRANDAO.pdf.jpg
bitstream.checksum.fl_str_mv 6f9af73efd4a662d65ea6b8b782b3d29
111b5721adaa88ef30d8f1c0d20dc225
5d0ce8d2845fdad750247bad562c2107
bitstream.checksumAlgorithm.fl_str_mv MD5
MD5
MD5
repository.name.fl_str_mv Biblioteca Digital de Teses e Dissertações do UFSM - Universidade Federal de Santa Maria (UFSM)
repository.mail.fl_str_mv atendimento.sib@ufsm.br||tedebc@gmail.com
_version_ 1801485255997128704